Figure 2.2.2.2

 Mounting Dimensions for the MCP 

2.2.3

 

Mounting 

The MCP is to be mounted to a flat vertical surface in 

line  with  Buildings  Codes  and  Regulations.  The  MCP  rear 
panel  (base)  is  attached  to  the  wall  with  two  screws.  The 
front  part  of  the  housing  is  installed  on  the  mounted  base 
after  connecting  wires  to  the  terminal  block.  The  wires  that 
pass under the rear panel should not be clamped by the MCP 
housing. 

Figure 2.2.3.1  shows  the  view  of  the  MCP  (without 

the protective flip cover). 

1:

 Hole to insert the key to reset the activated MCP; 

2:

 Holes to insert the key to open the MCP housing; 

3:

 Special key to reset the activated MCP / to open its housing; 

4:

 Place to apply a seal. 

 
 
 
 
 
 

Figure 2.2.3.1.

 Parts of the MCP 

 

Summary of Contents for IPR 513-3M

Page 1: ...CONVENTIONAL MANUAL CALL POINT IPR 513 3M User s Manual ...

Page 2: ...Safety Precautions 8 2 2 2 Design 8 2 2 3 Mounting 9 2 2 4 Wiring 10 2 2 5 Settings 10 2 2 6 Usage 10 2 2 7 Testing Operability 10 2 2 8 Extreme Situation Actions 10 2 2 9 Troubleshooting 11 3 Maintenance 12 3 1 General 12 3 2 Safety Precautions 12 3 3 Maintenance Schedule 12 3 4 Performance Testing 12 3 5 Technical Examination 13 3 6 Preservation Depreservation Represervation 13 4 Routine Repair ...

Page 3: ...pment or product Only the personnel who have studied this manual are allowed to operation activities All activities on mounting programming and commissioning shall be performed in compliance with the requirements of the regulatory documentation in force at the place of operation Abbreviations LED Light Emitting Diode MCP Manual Call Point ...

Page 4: ...Signal 10 Signal 20М or similar that provide loop voltage up to 30 V and limit the current in a loop at a level not exceeding 25 mA The functions of the MCP are as follows Monitoring the operating element for its conditions Sending messages to the control and indicating equipment Indicating operation conditions operating element s conditions with its built in LED The manual call point is intended ...

Page 5: ...equency range Max acceleration 1 35 Hz 0 5g 1 2 10 Environment category as per OST 25 1099 83 О3 1 2 11 Operating temperature range Minus 30 to 55 С 1 2 12 Relative air humidity Up to 93 at 40 С 1 2 13 Weight 0 15 kg max 1 2 14 Housing dimensions 95 91 34 mm max 1 2 15 Non stop operation 24 7 1 2 16 MTBF in the quiescent mode 80 000 hours min 1 2 17 Survival probability 0 98758 1 2 18 Expected lif...

Page 6: ...f the operating element pressing arming causes a change in the positions of the electric microswitch contacts The activated MCP is armed by means of the special housing key provided The typical wiring diagram for the MCP is shown in Figure 2 2 4 1 1 4 2 The MCP is supplied with power via the alarm loop of the control and indicating equipment which provides loop voltage up to 30 V and limits curren...

Page 7: ...screwdriver 3 0 50 mm Cross slot screwdriver 2 100 mm Side cutting pliers 160 mm Pliers 160 mm 1 6 Marking and Sealing Every IPR 513 3M has a marking placed inside its housing on the rear panel shown in Figure 2 2 2 2 The marking contains the name of the product its decimal number factory number the year and quarter of production and conformity marks The transparent protective flip cover can be se...

Page 8: ...afety including emergency operation in accordance with Russian standards GOST 12 2 007 0 75 and GOST 12 1 004 91 There are no potential hazard circuits within the MCP Do SHUT OFF power from the MCP before mounting installing and maintaining this one Mounting and maintenance of the MCP should be carried out by persons with the second or higher electric safety qualification level 2 2 2 Design The IP...

Page 9: ...g is installed on the mounted base after connecting wires to the terminal block The wires that pass under the rear panel should not be clamped by the MCP housing Figure 2 2 3 1 shows the view of the MCP without the protective flip cover 1 Hole to insert the key to reset the activated MCP 2 Holes to insert the key to open the MCP housing 3 Special key to reset the activated MCP to open its housing ...

Page 10: ...e of verification of knowledge of safety regulations The MCP is activated by pressing the operating element after flipping the clear protective cover While being activated the MCP reduces its internal resistance down to a value not above 500 Ohm Operation modes of the MCP and correspondent indications are shown in Table 2 3 1 Table 2 3 1 Operation Mode Description Indication Quiescent Mode MCP con...

Page 11: ...contacts and in case of zero voltage check the integrity of cables and contact joints No fire alarm after pressing the operating element No communications between the MCP and control and indicating equipment Check the integrity of cable and contact joints Internal circuitry malfunction Send the MCP for repair Structure defect of the MCP ...

Page 12: ...fire alarm on the input with the connected MCP shall be generated and the MCP shall indicate the fire alarm conditions 3 4 4 Reset the unit to the normal conditions by arming cocking the operating element via the special key Observe changing the MCP indication for indication of the normal conditions With the help of the network controller issue a comand to reset the alarm from the MCP 3 4 5 Perfor...

Page 13: ...13 3 5 Technical Examination Technical examination is not applicable for this equipment 3 6 Preservation Depreservation Represervation Preservation is not applicable for this equipment ...

Page 14: ...s 5 through 40 С and relative humidity up to 80 at 20 С 6 Transporting The product can be transported in a transport container at ambient temperatures minus 50 through 50 С and relative humidity up to 95 at 35 С 7 Disposal The equipment is to be disposed of considering that there are no toxic components in it The content of precious materials doesn t require accountability for storage retirement a...

Page 15: ...93 20 IPR 513 3M Conventional Manual Call Point meets the requirements of Technical Regulations TR EAEU 037 2016 On the restriction of the use of hazardous substances in electronic and radio electronic equipment and is covered by Conf Declaration ЕАЭС RU Д RU РА01 В 82301 19 The production of IPR 513 3M Conventional Manual Call Point is awarded with Conformity Certificate GOST R ISO 9001 The Certi...