The GTD20A uses an internal relay contact to control the AC power feeding the lighting load. When the generator (or 
central inverter) supplies AC power to the lighting fixture, the GTD20A bypasses the local switching means or dimmer. 
This ensures the lighting load will be energized at full lumen output during generator (or central inverter) operation 
regardless of switch position or dim setting.

No routine maintenance is required to keep the GTD20A functional. However, it should be checked periodically to 
ensure that it is working properly. Note: Make sure to disconnect both the normal and emergency panel circuit breakers 
before servicing. 

! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL !

STEP #3

FOLLOW-UP & QUICK TEST OF THE INSTALLATION

>  Mark each designated emergency lighting fixture with the warning labels provided (20 labels are provided 

with each unit).

>  Apply AC power to all circuits. The green "Normal Power Present" and the red "Emergency Power Available" 

LED's should be illuminated.

>  Perform a quick test as described on the unit label to check for proper operation. When the test  

 

button is depressed, the green "Normal Power Present" LED should extinguish and the controlled  

 

lighting load should illuminate regardless of the local switch position provided emergency power is  
available (check red LED).

>  During a quick test using a GTD20A with a dimming system, the lighting load should illuminate at  

full lumen levels when the test switch is depressed regardless of the lumen level during normal operation.

>  The entire generator (or central inverter) system, including all designated lighting loads, should be  

exercised to ensure proper operation (e.g., power up the generator, throw the main automatic transfer 
switch to the generator position, and check the lighting loads to verify they are operating properly from 
the generator/central inverter supply).

OPERATION

MAINTENANCE

6

ILLUSTRATION 9

WIRING DIAGRAM for UL 924 - SWITCH BYPASS Applications

INSTALLATION

4  5  6  7

1  2  3

NORMAL

CKT BKR

PANEL

SWITCHED

HOT TO

DIMMING

DRIVERS

NEUTRAL TO

DIMMING

DRIVERS

EMERGENCY

CKT BKR

PANEL

1  2    3  4    5  6  7

DIMMING

CONTROL

GTD20A

ELECTRONICS

COVER

T1* 

GTD20A TERMINAL BLOCKS 

T2*

HOT

PURPLE

HOT

NEUTRAL

SWITCHED HOT

NEUTRAL

* WIRE GAUGES FOR ALL LEADS 

   TERMINATING AT T2 SHOULD BE #18 AWG.

* JUMPER CONNECTIONS ON T1 AND T2 ARE 

   CONTRACTOR INSTALLED.

TO DIMMING

DRIVER

PURPLE

CONNECTIONS

(0 - 10VDC)

TO DIMMING

DRIVER

GRAY

CONNECTIONS

(0 - 10VDC)

BLK

BLK

GRAY

WHT  (IF PROVIDED)

GTD20A as a Switch Bypass Device with a 0-10 VDC Dimming System

Summary of Contents for GTD20A

Page 1: ...ch Circuit Emergency Lighting Transfer Switch BCELTS under UL 1008 or a Switch Bypass under UL 924 Use the proper wiring diagram in the appropriate section of these instructions 6 An unswitched normal AC power source 120 through 277 VAC 50 60 Hz and a direct separate connection to a generator supplied or central inverter system supplied emergency panel are required 7 The use of accessory equipment...

Page 2: ...cation using appropriate hardware not supplied See Illustration 1 for typical installation DO NOT MOUNT WITH LID FACING DOWN See Illustration 2 ILLUSTRATION 1 WALL MOUNTING STEP 2 INSTALLING THE GTD20A Disconnect AC power from all supply circuits Remove GTD20A lid and install necessary conduit and wiring not supplied to the GTD20A Refer to the illustrations on the following pages for proper wiring...

Page 3: ...Y LOCAL SWITCHING MEANS LIGHTING LOAD UP TO 20 A 1 2 3 4 5 6 7 HOT NEUTRAL NORMAL CKT BKR PANEL HOT NEUTRAL HOT NEUTRAL WIRE GAUGES FOR ALL LEADS TERMINATING AT T2 SHOULD BE 18 AWG JUMPER CONNECTIONS ON T1 AND T2 ARE CONTRACTOR INSTALLED 4 5 6 7 1 2 3 1 2 3 4 5 6 7 DIMMING RACK GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 EMERGENCY CKT BKR PANEL LIGHTING LOAD UP TO 20 A HOT NEUTRAL NORMAL...

Page 4: ...G DRIVER PURPLE LEADS TO DIMMING DRIVER GRAY LEADS PURPLE GRAY 1 2 3 4 5 6 7 GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 EMERGENCY CKT BKR PANEL LIGHTING LOAD UP TO 20 A HOT NEUTRAL NORMAL CKT BKR PANEL HOT NEUTRAL HOT NEUTRAL WIRE GAUGES FORALLLEADS TERMINATINGATT2 SHOULD BE 18AWG JUMPER CONNECTIONS ON T1AND T2ARE CONTRACTOR INSTALLED 0 10 VDC DIMMER BLK BLK WHT IF PROVIDED NOTE Wire ga...

Page 5: ...WITCHING MEANS GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 HOT HOT NEUTRAL NEUTRAL WIRE GAUGES FOR ALL LEADS TERMINATING AT T2 SHOULD BE 18 AWG JUMPER CONNECTIONS ON T1 AND T2 ARE CONTRACTOR INSTALLED 4 5 6 7 1 2 3 NORMAL CKT BKR PANEL DIMMED HOT TO DIMMING DRIVERS SWITCHED HOT TO DIMMING DRIVERS NEUTRAL TO DIMMING DRIVERS EMERGENCY CKT BKR PANEL 1 2 3 4 5 6 7 DIMMING CONTROL GTD20A ELEC...

Page 6: ... LED should extinguish and the controlled lighting load should illuminate regardless of the local switch position provided emergency power is available check red LED During a quick test using a GTD20A with a dimming system the lighting load should illuminate at full lumen levels when the test switch is depressed regardless of the lumen level during normal operation The entire generator or central ...