background image

4

EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT

TYPICAL SCHEMATICS ONLY.  CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.

TROUBLESHOOTING GUIDE

INDICATOR

LIGHT STATE

ERROR

CORRECTIVE ACTION

0x 

Flashes

Light On Steady

None

No Action. The Unit is Operating Correctly.

2x 

Flashes

Battery

Indicates that a self-test/self-diagnostic test did not meet full duration. 

1.  Charge the unit for the rated recharge time and perform a manual self-diagnostic    test.
2.  If error is still present then the battery is past end of life and should be replaced.

3x 

Flashes

Charging

1.  Check input AC mains wiring of Unswitched Hot, Neutral, and Ground.
2.  Verify Voltage and Frequency are stable and match the product’s input ratings on the label.

4x 

Flashes

Commissioning

During a self-test/self-diagnostic test, the unit detected the LED load has changed of more than 25% 
from the initial commissioned value.  

1.  Replace the LED Load and perform a manual self-diagnostic test. 
2.  If error is still present then recalibrate the commission value by deactivating the unit.  Apply AC 
mains to activate unit and it will recommission itself after one hour.

5x 

Flashes

Temperature

Product temperature is beyond its rated temperature range. 

1.  Ensure unit is within the rated temperature range stated on the product label. 
2.  Confirm by measuring at the Tc point on the product label.

Continuous Flashing

LED Load

Indicates a problem with the connected emergency LED load. 

1.  Check output wiring to the LED Load and verify polarity is correct.
2.  Check for Open or Short circuit on the output connections.
3.  Check Vf is within the rated output voltage range in emergency mode.   
4.  Ensure LED load is operational and specified for unit.

NOTE:

  

 

For short-term testing of the emergency function, the battery must be charged for at least one hour. 

 

  The emergency driver must be charged for at least 24 hours before conducting a long-term test.

WIRING DIAGRAMS

If the unit has encountered a problem after installation, then it will flash the error code with the indicator light.  Count 
the number of times the indicator is OFF to read the number of flashes.  Then use the troubleshooting steps to solve the 
issue.

Emergency

Driver

LED

Driver

AC

Mains

120

Ͳ

277Vac

50/60Hz

LED

LOAD

Grey
Grey
White
Green
White
Black

Black

Blue

Red

Black

+

Ͳ

Neutral
Line
Ground

LED

+

LED

Ͳ

Illuminated

Test

Switch

Wall

Switch

UL

Class

2

circuits

UL

Class

1

circuits

Internal

connections

Max

Current

=

3.

0

A

Switched

Line

Neutral

Unswitched

Line

Summary of Contents for BSL06M5

Page 1: ... gasketed fixtures Product is not suitable for heated air outlets outdoors wet or hazardous locations Maximum allowable case temp is 65ºC See the unit label for Tcase measurement location 6 An unswitched AC power source is required 120 277 VAC 50 60 Hz 7 Do not install near gas or electric heaters 8 Do not attempt to service the battery A sealed no maintenance battery is used that is not field rep...

Page 2: ...he voltage across the LED arrays when operating from the AC driver 3 Ensure the output current of the AC LED driver does not exceed 3 0 Amps 4 Ensure there will be sufficient light output in the end application Estimate the egress lighting illumination levels by doing the following a Find the efficacy of the LED load This can be given by the luminaire manufacture This number will be given in lumen...

Page 3: ...il the condition has been corrected and the unit passes the next test To deactivate the unit for storage or shipping press and hold the test button while the unit is in emergency mode until the LED load is turned off STEP 4 WIRING THE EMERGENCY DRIVER Select the appropriate wiring diagram to connect the emergency driver to the AC driver and LED load Make sure all connections are in accordance with...

Page 4: ...r 5x Flashes Temperature Product temperature is beyond its rated temperature range 1 Ensure unit is within the rated temperature range stated on the product label 2 Confirm by measuring at the Tc point on the product label Continuous Flashing LED Load Indicates a problem with the connected emergency LED load 1 Check output wiring to the LED Load and verify polarity is correct 2 Check for Open or S...

Reviews: