4.3  230V SINGLE PHASE 

– With CS-1 Controller (CS-1 Controller provides on / off / high heat / low heat / fan only settings). 

 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing.  
Drawings show connections inside the black terminal box on the outside of the heater and the inside of the CS-1 Controller. 

Do NOT use power tools to undo or do up terminal screws.

 

Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 
 
 

 

 

 

Standard Connection using CS-1 Controller 

Use 2.5mm² 3 Core Mains Cable (see note above). 
Use 2.5mm² 5 Core Cable to connect the heater to the CS-1 Controller (see note above). 
Remove  any  links 

that may be present in heater terminal box between terminals 1,2,3,4 or 5. 

 
Mains Cable 
Connect Brown wire 

– Terminal 1 or L. 

Connect Blue wire 

– Terminal 5 or N. 

Connect Green / Yellow wire 

– Terminal E or  

 

Heater to CS-1 Controller Cable 

– (Colours for reference only) 

Connect Brown wire 

– Terminal 1 or L of heater and Top Terminal L (Supply) on right DP Switch of CS-1. 

Connect Grey wire 

– Terminal 2 of heater and Centre switch Terminal COM of CS-1. 

Connect Blue wire (adding red or other suitable colour sleeve to both ends first) 

– Terminal 3 of heater and Terminal COM on Left SP Switch of CS-1. 

Connect Black wire 

– Terminal 4 of heater and Terminal L1 on left SP Switch of CS-1. 

Connect Green / Yellow wire 

– Terminal E or 

of heater and earth connection on CS-1. 

 
 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE 

 

 

 

 

 