2.
BATTERY DISPLAY PANEL
The integrated battery display panel displays the following variables:
3.
RECOVERY FROM OVER-DISCHARGE
If the batteries are over-discharge and left uncharged for a period of time, they will enter
protection mode. To recover the batteries from this mode, follow the procedure below:
-
Turn off battery circuit breaker(s) on the unit’s integrated DB.
-
Turn on mains supply breaker. You have to have a working mains supply.
-
Wait for 2 hours, then turn on the battery breaker(s). The inverter must start and charge the
battery with a positive current at this point. Reference the integrated battery display.
-
If the batteries are not charged, repeat steps 1 to 3 above.
-
Should the system not start up at this point, please contact BlueNova technical support.
F.
Emergency & First Aid
1.
IN CASE OF FIRE
a.
Evacuate danger zone. Open ventilation in the room if possible.
b.
Extinguish fire with a CO2 fire extinguisher.
c.
After the fire has been extinguished, immerse any remaining smoking cells completely in
water.
Wear protective gear during this procedure.
2.
SKIN CONTACT
a.
Wash the affected area immediately with soap and water.
b.
If irritation persists, seek medical attention.
3.
EYE CONTACT
a.
Rinse eyes immediately with clean water continuously for at least 15 minutes.
b.
Seek medical attention immediately afterwards.
4.
INGESTION
a.
Refrain from taking any emetic or vomit-inducing medicine.
b.
Seek medical attention immediately.
G.
Supporting documents