2.

 

Storage Instructions 
 

a.

 

Ensure that the battery is switched off when stored. 

b.

 

Disconnect the communication cable. 

c.

 

Always store batteries in a cool and well-ventilated area 

 ideally 25°C ± 3°C. 

d.

 

Store away from moisture and heat. 

e.

 

Do not store batteries upside down for overly long periods. 

f.

 

Check the open circuit voltage of stored batteries at least once per month. Recharge batteries sufficiently and 
frequently enough to prevent the open circuit voltage falling below 40V.  

g.

 

The battery needs to be charged every 6 months if out of use. 

h.

 

Ensure that the stored battery’s state of charge is always above 50%. 100% SOC is optimal.

 

i.

 

Don’t place more than 6 units on top of each other.

 

 
 

 

F.

 

TROUBLESHOOTING 
 

Please cross-

reference the behaviour of the battery’s LED indicators with the table below to determine whether 

your battery is operating correctly. Kindly contact BlueNova Technical Support for assistance if necessary. 

 

Battery Status 

State 

SOC Indicators 

RUN LED 

ALM LED 

 

 

 

 

 

 

Off 

Sleep mode 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

Stand by 

Normal 

Indicates state-of-charge 

ON 

OFF 

Warning 

Indicates state-of-charge 

ON 

Flash 2 

Protection 

Indicates state-of-charge 

OFF 

ON

 

Charging 

Normal 

Indicates state-of-charge 

Flash 1 

OFF 

Warning 

Indicates state-of-charge 

Flash 1 

Flash 2 

Protection 

Indicates state-of-charge 

OFF 

ON 

Discharging 

Normal 

Indicates state-of-charge 

Flash 2 

OFF 

Warning 

Indicates state-of-charge 

Flash 2 

Flash 2 

Protection 

Indicates state-of-charge 

OFF 

ON 

BMS Failure 

Sleep mode 

OFF 

OFF 

OFF 

OFF 

OFF 

Flash 2 

 

Flash 1

: LED flashes once every second  /  

Flash 2

 

 LED flashes once every 2 seconds 

 
 

G.

 

EMERGENCY & FIRST AID 
 

1.

 

In case of fire 

 
a.

 

Evacuate danger zone. Open ventilation in the room if possible. 

b.

 

Extinguish fire with a CO2 fire extinguisher. 

c.

 

After the fire has been extinguished, immerse any remaining smoking cells completely in water. 
Wear protective gear during this procedure. 
 

Summary of Contents for 52V RacPower Series

Page 1: ...User Manual 52V RacPower Range BN52V 100 5 2k BP with CAN communication Document Revision No Ver 1 0 1 Revision Date 2021 04 01 Approved by J P Verster...

Page 2: ...applicable to your battery or if you have any questions or comments kindly contact BlueNova Technical Support Office 27 21 205 2000 E mail support bluenova co za Please do not discard this document a...

Page 3: ...el will then flash from left to right Shut down Keep the RESET button depressed for 3 seconds while the battery is on LED s on the panel will then flash from right to left Reset Press the RESET button...

Page 4: ...0 A Maximum discharge Current limit 100 A Recommended discharge current limit 50 A IMPORTANT Inverter charger voltage calibration Some inverters chargers have been known to return inaccurate results w...

Page 5: ...ter Protocol configuration 1 2 3 4 5 6 Inverter OFF OFF Victron250 ON OFF Victron500 SMA Studer OFF ON Goodwe ON ON Reserved Note Ensure to have the same protocol configuration on all parallel units 1...

Page 6: ...nd unit then from the second unit to the third etc as illustrated above Wire diameter should be equal to or exceed 8mm 3 Connect the NEGATIVE terminals of the first top unit to the second unit then fr...

Page 7: ...the battery s LED indicators with the table below to determine whether your battery is operating correctly Kindly contact BlueNova Technical Support for assistance if necessary Battery Status State SO...

Page 8: ...va co za 2 Skin contact a Wash the affected area immediately with soap and water b If irritation persists seek medical attention 3 Eye contact a Rinse eyes immediately with clean water continuously fo...

Reviews: