User Manual
RacPower® BN52V-100-5.2k BP
2 Erica Way
Office:
+27 21 205 2000
Somerset West Business Park
Technical Support:
Somerset West, 7130
2.
Storage Instructions
a.
Ensure that the battery is switched off when stored.
b.
Disconnect the communication cable.
c.
Always store batteries in a cool and well-ventilated area
–
ideally 25°C ± 3°C.
d.
Store away from moisture and heat.
e.
Do not store batteries upside down for overly long periods.
f.
Check the open circuit voltage of stored batteries at least once per month. Recharge batteries sufficiently and
frequently enough to prevent the open circuit voltage falling below 40V.
g.
The battery needs to be charged every 6 months if out of use.
h.
Ensure that the stored battery’s state of charge is always above 50%. 100% SOC is optimal.
i.
Don’t place more than 6 units on top of each other.
F.
TROUBLESHOOTING
Please cross-
reference the behaviour of the battery’s LED indicators with the table below to determine whether
your battery is operating correctly. Kindly contact BlueNova Technical Support for assistance if necessary.
Battery Status
State
SOC Indicators
RUN LED
ALM LED
Off
Sleep mode
OFF
OFF
OFF
OFF
OFF
OFF
Stand by
Normal
Indicates state-of-charge
ON
OFF
Warning
Indicates state-of-charge
ON
Flash 2
Protection
Indicates state-of-charge
OFF
ON
Charging
Normal
Indicates state-of-charge
Flash 1
OFF
Warning
Indicates state-of-charge
Flash 1
Flash 2
Protection
Indicates state-of-charge
OFF
ON
Discharging
Normal
Indicates state-of-charge
Flash 2
OFF
Warning
Indicates state-of-charge
Flash 2
Flash 2
Protection
Indicates state-of-charge
OFF
ON
BMS Failure
Sleep mode
OFF
OFF
OFF
OFF
OFF
Flash 2
Flash 1
: LED flashes once every second /
Flash 2
–
LED flashes once every 2 seconds
G.
EMERGENCY & FIRST AID
1.
In case of fire
a.
Evacuate danger zone. Open ventilation in the room if possible.
b.
Extinguish fire with a CO2 fire extinguisher.
c.
After the fire has been extinguished, immerse any remaining smoking cells completely in water.
Wear protective gear during this procedure.