A
Appendix A: Gas Type Conversion
48
© Moffat Ltd, January 2007
Revision 1/
Blue Seal Evolution series G51 Gas Cooktops
Commissioning
Before leaving the converted installation;
1.
Check all gas connections for leakages using soapy water or other gas detecting equipment.
2.
Check the following functions in accordance with the operating instructions specified in the
“Operation” section of this manual.
•
Light the Pilot Burners.
•
Light the Main Burners.
•
Check the Low Fire burner operation.
•
Check the High Fire burner operation.
•
Check the Griddle Burner operation (If Fitted).
•
Ensure that all the controls operate correctly.
•
Ensure that the operating pressure remains correct.
NOTE: If for some reason it is not possible to get the appliance to operate correctly, shut off the
gas supply and contact the supplier of this appliance.
Gas Specifications
- Non-UK Only
WARNING
D
O
NOT
USE
A
NAKED
FLAME
TO
CHECK
FOR
GAS
LEAKAGES
.
Natural. Gas
LP Gas (Propane)
Open Burner
Main Burner Injectors
Ø 2.45 mm
Ø 1.50 mm
Pilot Burner ('PF' Option Only)
0.30
0.20
Griddle
Main Burner
Ø 2.10 mm
Ø 1.30 mm
Pilot Burner
0.35
0.23
Operating Pressure
0.95 kPa (*)
2.6 kPa (*)
Gas Regulator Cap Screw
Supply Pressure
1.13 - 3.40 kPa
2.75 - 3.40 kPa