2 I56-2769-020R
06-10
CANDELA SELECTION
Adjust the slide switch on the rear of the product to the desired candela set-
ting in the small window on the front of the unit. All products meet the light
output profiles specified in the appropriate UL Standards.
See Figures 1-3
.
Use
Table 1
to determine the current draw for each candela setting. For K
series products used outdoors at low temperatures, listed candela ratings must
be reduced in accordance with
Table 2
.
NOTE:
SpectrAlert products set at 15 and 15/75 candela automatically work
on either 12V or 24V power supplies. The products are not listed for 12V op-
erating voltages when set to any other candela settings. For 4-Wire products,
total current draw may be determined by adding current draw for the specific
candela selection and the current draw for the specific horn selection use
Table 1 and Table 3
.
TABLE 1. STROBE CURRENT DRAW (mA) FOR S, SC, P4 & PC4 SERIES:
Candela
8–17.5 Volts
16–33 Volts
DC
FWR
DC
FWR
Standard Candela Range
15
123
128
66
71
15/75
142
148
77
81
30
NA
NA
94
96
75
NA
NA
158
153
95
NA
NA
181
176
110
NA
NA
202
195
115
NA
NA
210
205
High Candela Range
135
NA
NA
228
207
150
NA
NA
246
220
177
NA
NA
281
251
185
NA
NA
286
258
TABLE 2. CANDELA DERATING:
Listed Candela
Candela rating at –40°F
(K Series Outdoor Applications Only)
15
Do not use below 32°F
15/75
30
75
44
95
70
110
110
115
115
135
135
150
150
177
177
185
185
HORN SELECTION
Turn the rotary switch on the back of the product to the desired setting. For
horn and 4-wire horn/strobe products, the current draw for each setting is
listed in
Table 3
. For 2-wire horn/strobe products (P2 series), current draws
are listed in
Tables 4
and
5
. The sound output measurement for each horn
setting is shown in
Table 6
.
TABLE 3. HORN CURRENT DRAW (mA) FOR H, P4 & PC4 SERIES:
Pos
Sound Pattern
dA Out
8–17.5 Volts
16–33 Volts
DC
FWR
DC
FWR
1
Temporal
High
57
55
69
75
2
Temporal
Medium
44
49
58
69
3
Temporal
Low
38
44
44
48
4
Non-temporal
High
57
56
69
75
5
Non-temporal
Medium
42
50
60
69
6
Non-temporal
Low
41
44
50
50
7
Coded
High
57
55
69
75
8
Coded
Medium
44
51
56
69
9
Coded
Low
40
46
52
50
NOTE:
In positions 7, 8, and 9, temporal coding must be provided by the NAC.
If the NAC voltage is held constant, the horn output will remain constantly on.
Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
FIGURE 2. LIGHT OUTPUT -
HORIZONTAL DISPERSION
Figures 1-3 list the minimum light output requirements per UL1971.
FIGURE 3. LIGHT OUTPUT - VERTICAL DISPERSION, WALL TO FLOOR
Degrees*
Percent of
Rating
0
100
5-25
90
30-45
75
50
55
55
45
60
40
65
35
70
35
75
30
80
30
85
25
90
25
Compound 45
to the right
24
Compound 45
to the right
24
Degrees*
Percent of
Rating
0
100
5-30
90
35
65
40
46
45
34
50
27
55
22
60
18
65
16
70
15
75
13
80
12
85
12
90
12
Degrees*
Percent of
Rating
0
100
5-25
90
30-45
75
50
55
60
45
65
35
70
35
75
30
80
30
85
25
90
25
*Tolerance of ±1 degree is permitted.
FIGURE 1. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS
TO FLOOR