IMPORTANT: Voltage calibration 

 

Experience has shown that some inverter/charger voltage measurement circuits are inaccurate. 

 

Compare the voltage values displayed by the inverter/charger with that of a calibrated voltmeter. 
If the actual voltage differs by more than 100mV from that measured by the inverter/charger, apply this 
difference to the highlighted values above (i.e. if actual voltage = 56V while inverter voltage = 56.5V, 
the voltage difference = 0.5V should be subtracted from each of the set values above). 

 

D.

 

TROUBLESHOOTING 

 

Every BlueNova® product contains integrated circuitry as a safety measure against possible damage 
from electrical malfunction. Under such conditions, the red Error LED on the Control Panel will flash to 
indicate a specific error. 

 

Before troubleshooting any errors, first check the following: 

 

 

Ensure that units are stacked in the correct order. Refer to Illustration 2A. 

 

Ensure that the signal cable and busbars are tightly connected. 

 

Ensure that fuses are fitted correctly and in working order (i.e. not 

blown

). 

 

The following table explains each error LED flash sequence, and the procedures to follow: 

 

Flash Seq.  Error 

Procedure 

1 x flash 

Fuse 

1.

 

Check fuses and replace with the same type if necessary. 

2 x flashes 

Comm Cable 

1.

 

Ensure all connections are securely tightened. 

3 x flashes 

Over-charge 

1.

 

Check settings on inverter / charger. Refer to C. Installation 

4 x flashes  Over-discharge 

1.

 

Check settings on inverter / charger. Refer to C. Installation 

2.

 

Ensure that the charger will switch on. 

3.

 

Keep Reset button depressed until battery switches on. 

No flashes 

Comm Cable 

1.

 

Check battery output & inverter input connections. 

2.

 

Ensure Comm cable connections are securely tightened. 

 

IMPORTANT: Deep Discharge Lockout (DDL) Mode 

 

BlueNova® batteries have been designed with protective countermeasures against malfunction and 
abuse. Whenever V 

low cut-off

 

is reached (refer to C. Installation), the battery will isolate itself 

automatically from the inverter/charger and load. The battery will enter 

Sleep Mode

 at this point, and 

may be switched on again by following the procedure detailed above for an over-discharged battery. 
 
Should a battery in Sleep Mode not be recharged within 8 weeks of switch-off date, the small load 
resulting from the standby circuitry will drain the battery sufficiently to result in the battery entering 

DDL Mode

. Recovery from DDL Mode is a lengthy process, and would involve a product recall to 

BlueNova® facilities as well as a service fee. See F. Battery Storage Guidelines for more information. 
 