4.- INSTALLATION AND START-UP
The manual you hold in your hand contains information and warnings that the user
should respect in order to guarantee a proper operation of all the instrument functions
and keep it in safety conditions. The instrument must not be powered on and used until
its definitive assembly is on the cabinet’s door.
If the instrument is not used
as manufacturer’s specifications, the protection of the
instrument will be damaged.
When any protection failure is suspected to exist (for example, it presents external visible
damages), the instrument must be immediately powered off. In this case contact a qualified
service representative.
4.1.- Installation
Mounting
PR200 series motor protector have two version installation mode, one for
CT separate installation,
another is CT integrated installation. Each instrument is to be mounted on panel (cut-out a mounting
hole). Keep all connections into the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to touch and cover
opening actions or elements removal may allow accessing dangerous parts. Therefore, the
instrument must not be used until this is completely installed.
Note:
This connection drawing is for reference only; the actual connecting terminal please refer to
the
label on the rear part.
CT separate installation
CT integrated installation
93mm
9m
m
96mm
74
mm
116.5mm
4
4.
5m
m
Φ20
107.7mm
6m
m
93
m
m
96.5mm
93
m
m
Φ
2
0
4
6
m
m
3
6
m
m
2
0
m
m
45.5mm
24mm
9mm
96
m
m
74mm