11. Technical Specifications

Line in (AC in)

Voltage in:  Rated AC voltage: 

100-240Vac

 

Rated DC voltage: 

140-300Vdc

 

Voltage Range: 

90-264Vac

 

 

130-300Vdc

 

Frequency: 

50Hz-60Hz

Current in:  Rated current: 

0.85A at 230Vac

 

Leakage current: 

typ. 550μA

 

Inrush current: 

<30Ap

 

Mains failure hold up time: >20ms

Output (DC out)

Voltage out: Rated voltage: 

24Vdc

 

Voltage range: 

22.0-28.8Vdc    

 

 

adjustable

 

Preset to: 

24.0Vdc 

 

Tolerance: 

2%

 

Residual ripple: 

<100mVpp (up to  

 

 

20kHz)

Current out:  

5A (Fig. 2)

 

Current limitation: 

over 1.1x I Rated

 

Behaviour with overload:  see Fig. 2

 

Efficiency/Power Losses 

Efficiency: 

typ. 90%

Power Losses: 

typ. 10W (230Vac/24Vdc 5A)

Power Losses max.: 

typ. 13W (90Vac/24Vdc 5A)

Device Protection

Internal Fuse: 

4AT/250Vac

Recommended backup fuse: circuit-breaker C10 resp. B10
for DC input voltage, an external DC fuse is necessary
Transient surge voltage protection: varistor

Input Connections (in:  L,N and PE)

WAGO MULTI CONNECTION SYSTEM 
Series 231, 3-pole, black
Type of wires: 

solid and stranded

Cross Section: 

AWG 28-14/0.08-2.5mm²

Stripped length: 

0.33inch/8-9mm

 

Output Connections (out: 2x   and 2x  )

WAGO MULTI CONNECTION SYSTEM 
Series 231, 4-pole, blue
Type of wires: 

solid and stranded

11. Technische Daten 

Eingang (ac in)

U in: 

AC Bemessungswert: 

100-240Vac

 

DC Bemessungswert:  

140-300Vdc

 

Bereich: 

90-264Vac 

 

 

130-300Vdc

 

Frequenz: 

50Hz-60Hz

I in: 

Bemessungswert: 

0,85A bei  230Vac

 

Ableitstrom: 

typ. 550μA

 

Einschaltstrom: 

<30Ap

 

Netzausfallüberbrückung:  >20ms

Ausgang (dc out)

U out: 

Bemessungswert: 

24Vdc

 

Bereich: 

22,0-28,8 Vdc einstellb.

 

voreingestellt auf: 

24 Vdc

 

Regelgenauigkeit: 

2%

 

Rippel: 

<100mVpp (bis zu  

 

 

20kHz)

I out: 

 

5A (Abb. 2)

 

Strombegrenzung: 

ab 1,1 x I Bemessung

 

Verhalten bei Überlast:  siehe Abb. 2

Wirkungsgrad/Verlustleistungen

Wirkungsgrad: 

typ. 90%

Verlustleistung:  

typ. 10W (230Vac/24Vdc 5A)

Verlustleistung max.: 

typ. 13W (90Vac/24Vdc 5A)

 

Absicherung

Interne Absicherung: 

4AT/250Vac

Empfohlene Vorsicherung:  Leitungsschutzschalter 
 

C10 bzw. B10

für DC Eingangsspannung ist eine externe DC Sicherung 
erforderlich
Transientenüberspannungsschutz: Varistor

Eingangs-Anschlussleitungen (in:  L,N und PE)

WAGO MULTISTECKERSYSTEM Serie 231, 3-pol., schwarz
Leiterart: 

Voll- oder Litzendraht

Querschnitt: 

0,08-2,5mm²/AWG 28-14

Abisolierlänge: 

8-9mm/0,33 inch

Ausgangs-Anschlussleitungen (out:  2x   und 2x  )

WAGO MULTISTECKERSYSTEM Serie 231, 4-pol., blau
Leiterart: 

Voll- oder Litzendraht

Querschnitt: 

0,08-2,5mm²/AWG 28-14

Abisolierlänge: 

8-9mm/0,33 inch

Abmessungen und Gewicht

B x H x T: 

67 x 120 x 133* mm

 

* incl. Anschlusssteckern

Gewicht: 

890g

Umgebungstemperatur / Luftfeuchtigkeit 

Betrieb: 

-10°C ... +70°C/30-85% RH 

 

ohne Betauung

Derating:  

-3%/K >50°C 

Verschmutzungsgrad: 

2 (nach EN 50178)

Klimaklasse: 

3K3 (nach EN 60721)

Kühlung

Die Gehäuseoberfläche darf nicht wärmer als +80°C 
werden.
Empfohlener Freiraum bei natürlicher Konvektion und 
horizontaler Einbaulage:   links/rechts: 15mm
 

oben/unten:  70mm

Sicherheit und Schutz

Schutzklasse: 

vorbereitet für Schutzklasse I

Schutzart: 

IP 20 nach EN 60529

Überspannugsschutz: 

max. 40Vdc

Überlastschutz: 

durch Strombegrenzung

kurzschlussfest: 

bei ca. 2 x I Bemessung

leerlauffest: 

ja

rückspeisefest: 

max. 30Vdc

SELV: 

IEC/EN 60950-1

PELV: 

EN 60204-1, EN 50178, 

 

IEC 62103, IEC 60364-4-41

Cross Section: 

AWG 28-14/0.08-2.5mm²

Stripped length: 

0.33inch/8-9mm

 

Dimensions / Weight

W x H x D: 

67mm x 120mm x 133*mm

 

*with terminals

Weight: 

890g

 

Environmental Conditions

Operation: 

-10°C ... +70°C/30-85% RH 

 

without dewfall

Derating: 

-3%/K >50°C

Contamination class: 

2 (in acc. with EN 50178)

Climatic class: 

3K3 (in acc. with EN 60721

 

Cooling

The housing surface temperature shall not 80°C.
The recommended spacing with natural convection and 
horizontal mounting: 

left/right: 15mm

 

above/below: 70mm

 

Safety/Protection

Safety class: 

prepared for safety class I

Protection index: 

IP 20 to EN 60529

Over voltage protection:  max. 40Vdc
Over load protection: 

current limited

Short circuit proof: 

at approx. 2 x I Rated

No load operation: 

yes

Feedback protection: 

max. 30Vdc

SELV: 

IEC/EN 60950-1

PELV: 

EN 60204-1, EN 50178, 

 

IEC 62103,  IEC 60364-4-41

Maße auf Tragschiene TH35

Abb. 1

Dimensions on Mounting Rail TH35

 

Fig. 1

Die Stromversorgung wird mit dem an der 
Rückseite eingesetzten Schieber auf dem 
oberen Schenkel der Tragschiene TH35 
angegesetzt. Die Aufrastung erfolgt durch 
Drücken der Stromversorgung in Richtung 
Tragschiene.

Place the unit with the steel catch at an 
angle behind the top edge
of the mounting rail TH35. Press the unit 
until it latches behind the
lower edge of the mounting rail.

Ausgangskennlinie

Abb. 2

Output Characteristic

Fig. 2

Blockdiagramm

Abb. 3

Block Diagram

Fig. 3

L

N

PE

F

dUa

LED

115

67

37

35

48

133

        5.0            9.0  Ia(Adc)

24

Ua(Vdc)

Max. Ausgansleistung 120W

Max. output power 120W

Ausgangsstrom

Output current

Summary of Contents for PSR 230/24-5

Page 1: ...re für 5 Minuten an Netzspannung anzulegen Permitted storage temperature 25 C 85 C Permitted humidity 30 85 relative humidity Residual humidity is not permitted Extended storage Equipment containing capacitors should be connected to the mains supply for at least 5 minutes every two years This equipment has to be protected against improper use Components are not to be bent or isolation spacing to b...

Page 2: ...ngsgemäßer Entwärmung horizontal zu montieren Abweichende Einbaulagen geschehen auf eigene Gefahr Wir empfehlen hierbei eine Ausgangsleistung von 50 und eine Umgebungstemperatur von 45 C nicht zu überschreiten Die Mindestabstände sind einzuhalten The power supply unit is designed for mounting rails TH35 in acc with EN 60715 For appropriate cooling the device has to be mounted in horizontal directi...

Page 3: ...n out 2x und 2x WAGO MULTISTECKERSYSTEM Serie 231 4 pol blau Leiterart Voll oder Litzendraht Querschnitt 0 08 2 5mm AWG 28 14 Abisolierlänge 8 9mm 0 33 inch Abmessungen und Gewicht B x H x T 67 x 120 x 133 mm incl Anschlusssteckern Gewicht 890g Umgebungstemperatur Luftfeuchtigkeit Betrieb 10 C 70 C 30 85 RH ohne Betauung Derating 3 K 50 C Verschmutzungsgrad 2 nach EN 50178 Klimaklasse 3K3 nach EN ...

Page 4: ...ße 36 46 27283 Verden Germany info block trafo de www block trafo de 12 Zulassungen 12 Approvals UL 60950 EMC CSA C22 2 Störaussendung Emission No 60950 1 03 EN 61000 6 3 E213214 Störfestigkeit Immunity EN 61000 6 2 UL 508 CSA C 22 2 No 14 95 E219022 Germanischer Lloyd ...