Blaze B100 Installation Instructions Manual Download Page 4

 

 

3.1.2  Corner Installation 

 

 

 

 

 

 

 

 

 

 

 

 

Corner Installation - minimum clearances 

Model 

 

 

 

B100  

(rear flue shield) 

400 

300 

B100 

(decro-mesh) 

400 

300 

*Decro-mesh installation requires a 490mm inner reflector 

 

3.2 

Floor Protector (Hearth) 

Unless the heater will be standing on a heat resistant floor 
such as concrete slab with slate or tiles, it will be necessary to 
provide a floor protector (hearth). 

The dimensions given above (Section 3.1) are the minimum 
required for the floor protector to extend beyond the firebox 
door opening. It must extend no less than 300 mm in front of 
the door opening, no less than 200mm either side of the door 
opening, and extend under the heater. 

It may be desirable, for example aesthetic reasons, for the 
floor protector to be larger than these minimum dimensions. 

The floor protector can be constructed of either: - 

a)

 

toughened glass no less than 10mm thick, OR 

b)

 

Non-combustible material no less than 7.5mm thick 
and with a thermal conductivity not greater than 
0.33W/m ⁰K, e.g. compressed cement sheet.  

The floor protector may be laid directly on the combustible 
floor. 

For more details and variations on floor protectors refer to 
AS/NZS 2918:2001 Clause 2.2, 3.3.1, & 3.3.2. 

 

 

 

If it is necessary to install a heater closer to a combustible 
surface than the stated requirements in Section 3 of this 
Installation Guide, it must be done in accordance with 
Australian Standard AS/NZS 2918:2001 Section 3, Tables 3.1 & 
3.2. 

Shield Construction: The shield shall be constructed from a 
heat resistant material. The shield must be fixed to the surface 
that requires protection and NOT the heater. 

The Standard allows three options to reduce stated 
clearances. 

 

Single layer of continuous material with Minimum Air Gap of 
12mm—Clearance Factor = 0.40 

Single layer of continuous material with Minimum Air Gap of 
25mm—Clearance Factor = 0.30 

Two spaced layers of continuous material with Minimum Air 
Gaps of 12mm + 12mm—Clearance Factor = 0.20 

The shielding must be open at the top and bottom (vented) to 
allow a continuous air flow. It is this air flow that keeps the 
surface requiring protection cool. Fixings should not impede 
this air flow. 

The shielding needs to go far enough along and up the wall so 
that the original side and rear required clearances are not 
compromised. As the flue is now closer to the wall the 
shielding should also protect the wall from the flue pipe. 

 

For example: 

Side wall clearance for the B100 is 700mm. 

A 12mm gapped shield on the wall with a factor of 0.40. 

Calculate: - 700mm x 0.40 = 280mm. This is the new side wall 
minimum clearance. 

The shielding needs to be large enough so that none of the 
original clearances of 700mm are compromised. 

 

 

 

 

 

 

 

4. REDUCING CLEARANCES TO COMBUSTIBLES 

Combustible Wall 

Co

mb

u

sti

b

le

 W

all

 

Summary of Contents for B100

Page 1: ...Installation Instructions Contemporary and Stylish Pecan Engineering Pty Limited proudly supports the activities of Landcare Australia through its membership of the AHHA B100 ...

Page 2: ...E INSTALLED IN ACCORDANCE WITH AS NZS 2918 2001 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODE OR CODES WARNING APPLIANCES INSTALLED IN ACCORDANCE WITH THIS STANDARD SHALL COMPLY WITH THE REQUIREMENTS OF AS NZS 4012 AS NZS 4013 WHERE REQUIRED BY THE REGULATORY AUTHORITY I E THE APPLIANCE SHALL BE IDENTIFIABLE BY A COMPLIANCE PLATE WITH THE MARKING TESTED TO AS NZS 4012 AS NZS 4013 ...

Page 3: ...rating Instructions for details 3 1 Positioning the Heater First review the necessary minimum clearances specified below before considering where to position the heater These clearances can be greater if desired Also check the practicability of installing the flue system in relation to any obstructing roof beams before positioning the heater These clearance distances can only be reduced if the sur...

Page 4: ...ated requirements in Section 3 of this Installation Guide it must be done in accordance with Australian Standard AS NZS 2918 2001 Section 3 Tables 3 1 3 2 Shield Construction The shield shall be constructed from a heat resistant material The shield must be fixed to the surface that requires protection and NOT the heater The Standard allows three options to reduce stated clearances Single layer of ...

Page 5: ...cro mesh The manufacturer s decro mesh locating ring must be used to support the decro mesh and inner shield up off the heater top It is important that air can be drawn into the base and rear of the decro mesh Place the locating ring above the flue spigot resting on the top plate and then place the first length of 150mm active flue into the spigot With the 490mm inner shield fitted inside the decr...

Page 6: ...ing it forward enough to clear the rear support rods 4 Once clear of the rear support rods push the baffle back so that it is resting hard up against the rear of the firebox 5 Centralise the baffle so that gaps between each side and firebox are equal 1 Place lower brick retainers in base of firebox centralised and against rear of the firebox 2 Place three bricks along the back 3 Place two medium s...

Page 7: ...7 Pecan Engineering Pty Limited 13 Acorn Road Dry Creek South Australia 5094 T 08 8349 8332 F 08 8260 6643 Email info pecan eng com au 12 TECHNICAL DRAWINGS ...

Reviews: