CONDENSATE DRAINAGE
The KOMFORT (EC) D5(B)180 heat recovery units require condensate drainage.
The hole for the drain pipes is in the cover of the unit.
CAUTION! The drain pipe on the side of the intake air from the street is designed to drain condensate, which forms when the
intake air is cooled in the heat exchanger if the unit is operating in a warm, humid climate. The decision on the need to install
this drain pipe must be made by the design engineer based on the operating conditions of the unit and the local climate. In
case of doubt or if there is a risk of condensate formation, the drain pipe on the intake air side must be installed for safety
reasons.
Remove the service panel and remove the plugs from the holes. When mounting according to the Diagram 1 install the drain pipe from
the delivery set into the hole. When mounting according to the Diagram 2 set the L-shaped drain pipe from the delivery set into the hole.
Seal the connections using sealant or other materials.
The drain pipes should be installed only in the holes indicated on the diagrams. For suspended and wall mounted horizontal installation
use two holes on the side of the unit, for a wall-mounted vertical installation use a hole at the bottom of the unit. Do not mount the drain
pipes in the holes not indicated on the installation diagram.
Drain hole location in case of mounting according to the Diagram 1
Drain hole location in case of mounting according to the Diagram 2