Condensate drain pipe

U-trap (hydraulic lock)

Sewage system

min 3 

15

/

16

 

min 1 

15

/

16

 

min 3°

Pipe

model

a [inch]

B [inch]

СIVIC EC LB(E/E2)300 

23  

5

/

8

13  

3

/

4

»

СIVIC EC LB(E/E2)300-E 
СIVIC EC LB(E/E2)500 

31  

1

/

2

13  

3

/

4

»

* the dimension may be increased during adjustment of the unit by means of the 
levelling feet 

The levelling feet on the bottom of the unit ensure exact alignment of the unit during 
mounting. 
For alignment of the unit loosen the nuts and adjust position of the support disc manually 
using a wrench. Then tighten the upper and the lower nut. 
To attain the best performance of the unit and to minimise turbulence-induced air 
pressure losses while mounting connect straight air duct sections to the unit spigots.
Minimum straight air duct length:
•  equal to 1 air duct diameter on outside side
•  equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected at any unit spigot, protect the unit inner 
parts from ingress of foreign objects by installing a protecting grille or other protecting 
device with mesh side width not more than 1/2 inch to prevent uncontrollable access to 
the fans. 
Fasteners for the unit mounting are not included into delivery set and should be ordered separately. 
While selecting appropriate fasteners consider material of the mounting surface as well as the weigh of the unit, refer to the technical data. For selection of the fasteners for unit 
mounting please refer to a service technician. 