STORAGE AND TRANSPORTATION REGULATIONS

•  Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range 

from +5 °C to + 40 °C and relative humidity up to 70 %.

•  Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing 

deformation.

•  Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
•  Follow the handling requirements applicable for the particular type of cargo.
•  The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and 

mechanical damage. The unit must be transported only in the working position.

•  Avoid sharp blows, scratches, or rough handling during loading and unloading.
•  Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at 

least 3-4 hours.

TROUBLESHOOTING

Problem

Possible reasons

Troubleshooting

The fan(s) do(es) not 
start.

No power supply.

Make sure the power supply line is connected correctly, 
otherwise troubleshoot the connection error.

Jammed motor.

Disconnect the fan from power supply. Troubleshoot 
the motor jamming. Restart the fan.

The fan has overheated.

Disconnect the fan from power supply. Eliminate the 
cause of overheating. Restart the fan.

Automatic circuit 
breaker tripping 
following the fan 
turning on.

High current consumption due to short circuit in 
power line.

Turn the fan off. Contact the Seller.

Noise, vibration.

The fan impeller is soiled.

Clean the impellers.

The fan or casing screw connection is loose.

Tighten the screw connection of the fan or the casing 
against stop.

The ventilation system components (air ducts, 
diffusers, louvre shutters, grilles) are clogged or 
damaged.

Clean or replace the ventilation system components 
(air ducts, diffusers, louvre shutters, grilles).

Summary of Contents for Primo 200

Page 1: ...Inline mixed flow fan USER S MANUAL EN Primo 200 Primo 250...

Page 2: ...13 Installation certificate 13 Warranty card 13 This user s manual is a main operating document intended for technical maintenance and operating staff The manual contains information about purpose tec...

Page 3: ...cky substances or fibrous materials Do not use the unit in a hazardous or explosive environment containing spirits gasoline insecticides etc Do not close or block the intake or extract vents in order...

Page 4: ...cautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel burning appliances Ensure that the unit is switched off from the supply mains before removi...

Page 5: ...ents favourable for the formation of hazardous substances toxic substances dust pathogenic germs Name Number Fan 1 pc User s manual 1 pc Packing box 1 pc Plastic screwdriver for the models with a time...

Page 6: ...ngress protection rating against access to hazardous parts and water ingress is IP 4 The unit is rated as a class I electric appliance The unit design is constantly being improved thus some models may...

Page 7: ...e straight air duct section to the spigots on both sides of the unit while mounting Minimum recommended straight air duct section length is equal to 3 fan diameters see the Technical data section If t...

Page 8: ...control voltage application to input terminal LT by an external switch e g indoor light switch After the control voltage is off the fan continues to operate within the set time period adjustable from...

Page 9: ...e connection must be made using durable insulated and heat resistant conductors cables wires The actual wire cross section selection must be based on the maximum load current maximum conductor tempera...

Page 10: ...Do not use water aggressive solvents or sharp objects as they may damage the impeller It is forbidden to remove or change the location of the balancers on the impeller as this can lead to increased le...

Page 11: ...wer up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours TROUBLESHOOTING Problem Possible reasons Troubleshooting The fan s do es not s...

Page 12: ...Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual includi...

Page 13: ...ATION CERTIFICATE The Primo_________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s F...

Page 14: ...Primo 14 www blaubergventilatoren de...

Page 15: ...www blaubergventilatoren de Primo 15...

Page 16: ...www blaubergventilatoren de B208 1EN 01...

Reviews: