CONDENSATE DRAINAGE
The KOMFORT Ultra D 105 units are equipped with an enthalpy heat exchanger and do not require condensate drainage.
The KOMFORT Ultra D 105-A units are equipped with a drain pan for condensate collection and removal.
Temperature differences between supply and extract air flows in heat recovery units lead to condensate formation. Condensate is
collected in the drain pan and is removed outside by the drain pipes.
Connect the part of the pipe going from the unit outlet to the sewage system.
min 3°
WARNING!
To ensure water drainage, pipes should be mounted with a slope of at least 3°.
Provide free drainage for the condensed water, otherwise it is accumulated inside the unit that may cause the equipment damage and
condensate outflow to the room.
The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C!
If the expected ambient air temperatures are below 0 °C the condensate drainage system must be equipped with heat insulation and
pre-heating facilities.
Condensate drain pipe
Pipe
U-trap
Sewage system