10
www.blaubergventilatoren.de
KOMFORT EC L S6
Fig. 4. Unit mounting to the floor
Fig. 5. Unit suspended mounting
The unit mounting on the floor is shown in fig. 4.
The unit is mounted to the ceiling by means of the belts. Make sure the belt
load carrying capacity corresponds to the unit weight. The belts are attached
to the unit using triangular screws either through the holes or through a
clamp. The suspended unit mounting example is shown in fig. 5.
Rigidly fixed cross beam
Belt fixation spot
CONDENSATE DRAIN
The drain pan is equipped with a drain pipe for condensate removal outside
the unit.
Connect the drain pipe, the U-trap (not included into the delivery set) and a
sewage system with metal, plastic or rubber drain hoses, fig. 6.
While laying the hoses provide the slope downward min. 3 %.
Fill the system with water prior to connecting it to power supply. The U-trap
must always be filled with water.
Before starting the unit fill the drain system with water and keep the U-trap
always filled with water. Provide free drainage for the condensed water,
otherwise it is accumulated inside the unit which may result in the equipment
damage and condensate outflow to the room.
The condensate drain system is suitable for indoor frost-free application
with the ambient temperature above 0 °C.
If the expected ambient temperature is below 0 °C provide heating for
the drain system.
WARNING
In case of several unit mounting connect each unit to an individual U-trap. Direct condensate withdrawal with no connection
to the drain system is not allowed.
!
Fig. 6. Condensate drainage
Drain pipe
Connecting hose
U-trap
Connecting hose
Sewage system
min 3°
А
В
А=В ≈ 60 mm