STORAGE AND TRANSPORTATION REGULATIONS

•  Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range 

+5 ˚C...+40 ˚C  and relative humidity up to 70 %.

•  Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing 

deformation.

•  Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
•  Follow the handling requirements applicable for the particular type of cargo.
•  The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and 

mechanical damage. The unit must be transported only in the working position.

•  Avoid sharp blows, scratches, or rough handling during loading and unloading.
•  Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at 

least 3-4 hours.

TROUBLESHOOTING

IF UNIDENTIFIED NOISES OR ODOURS SHOULD ARISE AND IN CASE OF DEFORMATION 

OF ELEMENTS, VIBRATION, TERMINATION OF AIR SUPPLY/EXTRACTION OR REDUCED 

SYSTEM PERFORMANCE, IMMEDIATELY DISCONNECT THE UNIT FROM POWER SUPPLY 

AND CONTACT THE SELLER FOR THE VENTILATION SYSTEM DIAGNOSTICS.

DIAGNOSTICS MUST BE CARRIED OUT BY QUALIFIED SPECIALISTS

POSSIBLE REASONS AND TROUBLESHOOTING

Problem 

Possible reasons 

Troubleshooting

The fan(s) does (do) not 
start when the unit is on.

No power supply.

Make sure the power supply line is connected correctly, 
otherwise troubleshoot the connection error.

The mode in which the fans are turned off is set.

Change the mode with the help of the control panel.

Low air flow.

Low set fan speed. 

Set higher speed. 

The filters and the fans are clogged, the heat exchanger 
is clogged.

Clean or replace the filters, clean the fans and the heat 
exchanger.

The ventilation system elements (air ducts, diffusers, 
louver shutters, grilles) are clogged, damaged or closed.

Clean or replace the ventilation system elements, such as air 
ducts, diffusers, louvre shutters, grilles.

Cold supply air.

The extract filter is soiled. 

Clean or replace the extract filter.

High noise, vibration.

The fan or casing screw connection is loose.

Tighten the screw connection of the fans or the casing.

No anti-vibration connectors on air duct pipe flanges.

Install anti-vibration connectors.

Water leakage.

The drainage system is soiled, damaged, or installed 
incorrectly.

Clean the drain line. 
Check the drain line slope angle. Make sure that the U-trap is 
filled with water and the drain pipes are frost protected.

If troubleshooting steps have failed,  

contact the Seller of the product.

In case of faults not described in the table,  

contact the Seller for further information.

Summary of Contents for KOMFORT EC DBW 2000

Page 1: ...Heat recovery air handling unit USER S MANUAL EN KOMFORT EC DBW 2000 KOMFORT EC DBW 3000...

Page 2: ...t the time of the document s preparation The Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest t...

Page 3: ...he receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation operations Unpack the unit with care The unit must be grounded W...

Page 4: ...explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open t...

Page 5: ...e mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pa...

Page 6: ...rs The unit design is constantly being improved thus some models may be slightly different from those described in this manual TECHNICAL DATA MODEL KOMFORT EC DBW 2000 KOMFORT EC DBW 3000 Supply volta...

Page 7: ...3000 7 OVERALL DIMENSIONS OF THE UNIT L1 D d L H H2 H1 B B2 B3 B2 B1 B1 Dimensions mm Model D B B1 B2 B H H1 H2 L L1 d KOMFORT EC DBW 2000 312 950 405 225 500 762 367 501 1400 1452 9 KOMFORT EC DBW 30...

Page 8: ...control system components OPERATING LOGIC Extract air Supply air Intake air Exhaust air The basic unit delivery set includes a control panel for connection to the control system inside the unit casin...

Page 9: ...Example Nut Washer Vibration absorbing rubber Nut and lock nut To attain the best performance of the unit and to minimise turbulence induced air pressure losses connect a straight air duct section on...

Page 10: ...damper 5 Boiler 6 Regulating valve of the heater with an actuator 7 Non return valve 8 Coarse filter 9 Water pressure sensor nc HEAT MEDIUM REGULATING VALVE ACTUATOR Caution The unit operates in two...

Page 11: ...ernative for dealing with resonance CONDENSATE DRAINAGE The drain pan is equipped with two drain pipes for condensate removal outside the unit Connect the drain pipe the U trap not included in the sta...

Page 12: ...the power and the ground cable route the cables through the airtight electric lead in in the unit casing and connect these to the terminal block The wiring diagram for connection of the air handling u...

Page 13: ...at exchanger maintenance once per year Some dust may accumulate on the heat exchanger even in case of regular maintenance of the filters To maintain high heat recovery efficiency regular cleaning is r...

Page 14: ...d particles Pour some water inside the drain pan and check the pipe for clogging Clean the U trap and drain pipe if required 5 Air intake maintenance twice a year Leaves and other pollutions can clog...

Page 15: ...M DIAGNOSTICS DIAGNOSTICS MUST BE CARRIED OUT BY QUALIFIED SPECIALISTS POSSIBLE REASONS AND TROUBLESHOOTING Problem Possible reasons Troubleshooting The fan s does do not start when the unit is on No...

Page 16: ...ntact the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manua...

Page 17: ...ALLATION CERTIFICATE The KOMFORT EC DBW ____________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installatio...

Page 18: ...www blaubergventilatoren de KOMFORT EC DBW 2000 3000 18...

Page 19: ...www blaubergventilatoren de KOMFORT EC DBW 2000 3000 19...

Page 20: ...www blaubergventilatoren de B225 2EN 01...

Reviews: