background image

 

501-K00    Page 6/12 

OPERATION 

 

Operation without guards in place can 
cause serious personal injury, major 
property damage, or death. 

 

Do not operate 

without guard 

in place 

 

 

 

Failure to relieve system pressure prior 
to performing pump service can cause 
serious personal injury or property 
damage.

  

Systems with meters will still 

be pressurized even after the hose is 
emptied

 

 

Hazardous pressure 

can cause serious 

personal injury or 

property damage

 

 

 

Disconnecting fluid or pressure 
containment components during pump 
operation can cause serious personal 
injury or property damage.

 

 

Hazardous pressure 

can cause serious 

personal injury or 

property damage 

 

 

 

Pumps operating against a closed valve 
can cause system failure, personal injury 
and property damage  

 

Hazardous pressure 

can cause personal 

injury or property 

damage 

 

PRE-START UP CHECK LIST 

1.  Inspect complete piping system and supports to ensure 

that no piping loads are being placed on the pump. 

2.  Verify proper coupling alignment. 

3.  Install pressure gauges in the 1/4" NPT intake and 

discharge ports located on the pump casing to check 
pump performance after start-up. 

4.  Ensure all valves and fittings in piping system are in the 

start-up or operating positions. 

5.  Jog the pump motor to verify proper pump rotation.  If 

rotation is incorrect, reverse rotation of motor. 

START UP PROCEDURES 

NOTICE 

Consult the "Troubleshooting" section of this manual if 
difficulties during start up are experienced. 

1.  Start the motor.  Priming should occur within one minute. 

2.  Check the pressure gauges to ensure the system is 

operating within expected parameters.  Record the 
gauge readings in the "Initial Start Up Information" 
section of this manual for future reference. 

3.  Inspect piping, fittings, and associated system equipment 

for leaks, noise, vibration and overheating. 

4.  Check the flow rate to ensure the pump is operating 

within the expected parameters.  Record flow rate in the 
“Initial Start Up” section of this manual. 

5.  Close the discharge valve and check the differential 

pressure across the pump.  It should not exceed the 
pressure setting of the external bypass valve. 

6.  With the discharge valve still closed, momentarily close 

the manual shut-off valve in the bypass return line to 
check the pump relief valve.  The pressure should be at 
least 25 PSI (1.7 bar) higher than the maximum system 
operating pressure or the system pressure control valve 
setting. 

7.  The external bypass valve must always be set at least 25 

PSI (1.7 bar) lower than the internal pump relief valve.   

NOTE - 

The normal operating pressure should be at 

least 5 - 15 PSI (0.3 -1.0 bar) less than the external 
bypass setting.  Pump speeds which result in higher 
pressures (nearing the valve setting) forces the liquid to 
be recirculated, creating excessive wear on the pump 
and equipment. 

 
 
 

Summary of Contents for LGL154C

Page 1: ...his symbol on the product or in the manual look for one of the following signal words and be alert to the potential for personal injury death or major property damage Warns of hazards that WILL cause...

Page 2: ...th Hazardous or toxic fluids can cause serious injury Do not operate without guard in place PUMP DATA PUMP IDENTIFICATION A pump Identification tag containing the pump serial number I D number and mod...

Page 3: ...t least four times the area of the intake piping Strainers must be cleaned regularly to avoid pump starvation Strainers are optional when pumping from underground tanks 4 The intake and discharge pipi...

Page 4: ...liquefied gas pumps and are included in the boundary jurisdiction of the pump Refer to Form 589 DO NOT pipe the bypass valve back to the intake line The setting on the external bypass valve should be...

Page 5: ...piping as short as possible Install the pump directly over the tank and as close to the ground as possible Minimize the Number of Fittings Every fitting valve and piece of straight piping causes a pre...

Page 6: ...reverse rotation of motor START UP PROCEDURES NOTICE Consult the Troubleshooting section of this manual if difficulties during start up are experienced 1 Start the motor Priming should occur within o...

Page 7: ...Capscrews Ft lbs 20 N m 27 Bearing Cap Capcrews 28 Ft lbs 20 N m 27 STRAINERS Strainers must be cleaned regularly to avoid pump starvation Schedule will depend upon the application and conditions LUBR...

Page 8: ...and bearing outer race 4 Carefully pull the rotating seal assembly consisting of seal jacket 153C rotating seal face and rotating O ring 153B 153E from the shaft Remove and discard the rotating O ring...

Page 9: ...f grease seal must face outside of head with spring and lip side facing inside of head 8 Install bearing spring 24C in inboard head 20 9 Install outer race of bearing 24 into bearing pocket in inboard...

Page 10: ...d of the shaft with the polished face of the stationary seat Center the head on the pump casing 12 Install and uniformly tighten all six head capscrews 21 and torque per Torque Table 1 30 Turn the pum...

Page 11: ...d discharge line 3 Pump not securely mounted 4 Improper drive line truck mounted pumps See Pump Drive 5 Misalignment of pump reducer or motor base mounted pumps 6 Bearings worn or damaged 7 Vibration...

Page 12: ...r com for complete information on all Blackmer products 1809 Century Avenue Grand Rapids Michigan 49503 1530 U S A Telephone 616 241 1611 Fax 616 241 3752 E mail blackmer blackmer com Internet Address...

Reviews: