KB-130-6
19
ter system and in low temperature applications requires
individual consultation with BITZER.
The use of the 2MTE-4K .. 6CTE-50K compressors
with motor version 1 as parallel compressors is pos-
sible. However, with regard to the lubrication condi-
tions, the gas suction superheat should not fall below a
minimum value of 10 K. The partial load range or the
switching to the operation with flash gas bypass is of
particular importance for the evaluation of the lubrica-
tion conditions. If necessary, a heat exchanger should
be used to minimise the refrigerant concentration in the
oil. Consultation with BITZER is recommended.
The use of compressors with motor version 2 as paral-
lel compressors requires individual consultation with
BITZER.
Filter drier
The solubility of water in gaseous CO
2
is much lower
than in other refrigerants. This means that a relatively
small amount of moisture can freeze out of the refriger-
ant and block or clog the regulation valves, particularly
in low temperature applications. Therefore a gener-
ously sized filter drier and a sight glass with moisture
indicator for CO
2
are necessary. Observe the maximum
operating pressures of the filter driers! The application
may possibly be limited to the liquid line after the inter-
mediate pressure receiver or the suction side (for sys-
tems without intermediate pressure receiver).
4 Mounting
4.1
Vibration damper
The compressor may be rigidly mounted if there is no
danger of fatigue fractures in the pipeline system con-
nected to it. Otherwise the compressor must be moun-
ted on vibration dampers.
Mounting the suction gas and discharge gas lines:
• Mount compressor on the vibration dampers or ri-
gidly. In this position (= operational position), con-
nect the suction gas and discharge gas lines and
make sure that they are stress-free. For a selection
of the vibration dampers see table 2, page 19.
Compressor
Kit number, article number (4 pieces)
Hardness
2MTE-4K .. 2KTE-7K
370 005 02
60 Shore
4PTC-6K .. 4KTC-10K
370 005 02
60 Shore
4JTC-10K .. 4CTC-30K
370 005 03
55 Shore
6FTE-35K .. 6CTE-50K
370 005 03
55 Shore
4PTC-7.F3K .. 4KTC-10.F4K
370 000 20
55 Shore
Tab. 2: Vibration dampers 2MTE-4K .. 6CTE-50K and 4PTC-7.F3K .. 4KTC-10.F4K
4.2
Shut-off valves / weld connections
Compressor
Shut-off valve article no. Designation
Inside diameter
d
i
Outside dia-
meter d
a
2MTE .. 2KTE
4PTC .. 4KTC
361 367 18
"Brazed/welded connection"
Ø19 .. 25.4
19 mm
25.4 mm
361 367 19
Swagelok valve 18 mm
18 mm
Swagelok
4JTC .. 4CTC
361 367 20
"Brazed/welded connection"
Ø10.1 .. 14
10.1 mm
14 mm
361 367 21
"Brazed/welded connection"
Ø16.1 .. 22
16.1 mm
22 mm
361 367 23
"Brazed/welded connection"
Ø22.4 .. 30
22.4 mm
30 mm
6FTE .. 6CTE
361 367 22
Swagelok valve 28 mm
28 mm
Swagelok
Summary of Contents for 2KTE-7K