7.3 Shutting down the system
Switch off the mains switch to shut down the pressure booster system.
Das System und der Membrandruckbehälter stehen immer noch unter Druck.
The pumps can be shut down individually by switching off the corresponding circuit breakers.
Die Leitungen vor dem Netzschalter stehen immer noch unter Spannung.
Die Netzschalter verriegeln, um unbeabsichtigtes Einschalten zu vermeiden.
When you have carried out the mechanical
and electrical installation described in section
6, proceed as follows:
1. Switch off the power supply with the main
switch.
Switch off the circuit breakers of all
pumps.
2. Connect water and power supplies to the
system.
3. Open all pump suction valves.
4. Close all pump discharge valves.
5. Prime all pumps and the suction pipe.
6. Switch on the power supply with the main
switch.
7. Start pump 1 by pressing the start/stop
button on the pump control panel.
8. Vent pump 1 by means of the air vent
screw.
9. Slowly open the discharge valve approxi-
mately 50 %.
10. Repeat steps 7 and 9 for the other pumps
in the system.
11. Slowly fully open all pump discharge
valves.