BIOLAN GREYWATER FILTER 125 Instructions For Installation, Use And Maintenance Manual Download Page 6

EN-4

EN

2.4 Conducting wastewater to the 

filter

The wastewater is conducted directly to the filter alternatively by 

gravity, by flow drainage or by a pump well. To ensure an even 

distribution, the inlet pipe should be provided with a straight 

80cm-long part before the branch sleeve (part 7), that reduces 

turbulence of the incoming water flow. 

If you intend to utilise existing septic tanks during pumping, 

these should be in good condition and hermetically sealed. The 

operation of the pump must be sequenced using a timer so that 

during one sequence the pump will feed at maximum 20 litres 

of wastewater to the filter. The interval between the sequences 

must be at least 10 minutes. The Biolan Timer, the Submersible 

Pump and the Pump Well are available as an option.

2.5 Discharge point for the 

wastewater

Conduct the treated wastewater to a suitable discharge point, 

for example a stone pocket or an open ditch. When planning, 

bear in mind that the discharge of wastewater should be unob-

structed even when the level of the surface water or groundwa-

ter is high. If you route the water to an open ditch, provide the 

end of the pipe with a flap or a net to prevent rodents or other 

small animals from gaining access.

Toxic

Hazardous to 

the environ-

ment

Corrosive

Inflammable

Oxidizing

3. Installation

Place the filter on a firm and even surface that is not susceptible 

to frost, such as, for example, a bed of gravel or crushed stone 

or a cast concrete slab. The filter must be in a horizontal posi

-

tion both lengthwise and laterally to allow the wastewater to flow 

smoothly over the entire cleaning area of the filter material.

3.1 Connecting the inlet and outlet 

sewer pipes

While installing gravity flow sewers, a sufficient gradient (of at 

least 1-1,5 %) needs to be provided to allow the wastewater to 

flow without obstruction from the sewer outlet of the house all 

the way to the discharge point.
There are inlet and outlet connectors for 75 mm sewer pipes on 

both sides of the filter. Depending on the requirements of the 

location, the pipes can be installed on either side. Connect the 

sewer pipe coming from the building to the inlet connector at 

upper edge of the filter. Connect the discharge sewer pipe to the 

outlet connector at its lower edge. Close the unused openings 

using plugs (product number 571513).

If the filter will be used in winter, the inlet sewer must be insu

-

lated. Whether also the outlet sewer needs to be insulated, shall 

be considered case by case.

3.2 Putting the filter material in place

The filter material is packed in plastic bags for transportation. 

Remove the plastic bags. Rip the filter material loose and spread 

it evenly across the boxes by tapping it gently. Resulting from 

the packaging method, the bags may contain excessive amount 

of filter material. The filling grade of the box is suitable when the 

surface of the filter material lies about 2 cm lower than the brim 

of the box. Finally, draw the filter material about 5 cm to the rear 

from the V-openings in the discharge end of the box.

The filter material boxes are identical, but their direction should 

be  observed  –  in  the  uppermost  box  water  flows  towards  the 

rear wall, in the next box it flows towards the service door etc. In 

the lowermost box water flows towards the rear wall, from where 

it falls along the shaped bottom into the discharge sewer.

4. Use and maintenance

The unit must be used and maintained in accordance with the in-

structions, and its operation must be monitored regularly. Main-

tenance of the wastewater system also involves maintenance of 

the pump well and the septic tanks, if provided. 

Into the filter can be conducted washing waters and waters from 

sauna as well as dishwashing and laundry waters. The filter tol

-

erates a small amount of anti-bacterial or chlorine-based agents 

that are commonly used for cleaning. Follow the dosing instruc-

tions issued by the manufacturer of the detergent. 
Wastewater from a WC or a dry toilet, rain water or stormwater, 

or drain water from foundations must not be conducted into the 

filter. Toxic chemicals or substances that contain such chemi

-

cals, which can kill the micro-organisms that clean the waste-

water, such as drain openers, paints, oils or solvents, must not 

be conducted into the filter. Harmful chemicals can be identified 

from the markings on their packaging:

3.3 Opening the air valves

The operation of the filter is based on activity of the micro-or

-

ganisms. These micro-organisms need oxygen to survive, and 

therefore,  it  is  vital    to  provide  the  filter  with  sufficient  air  ex

-

change. There are two adjustable disk valves for air exchange in 

the rear wall of the modules. Set both disk valves of the module 

about 10–20 mm ajar for the summer. In winter keep the valves 

only slightly ajar (about 5–10 mm). If you have realised the air 

exchange by means of sewer ventilation, keep the air valves 

completely closed to avoid odour problems (see point 2.3). 

Summary of Contents for GREYWATER FILTER 125

Page 1: ...70571500 BIOLAN GREYWATER FILTER 125 Instructions for installation use and maintenance EN 05 2014 Serial No Assembler Date of manufacture Seller s stamp signature and date of purchase...

Page 2: ...2...

Page 3: ...ing the filter material EN 5 4 3 Storing the filter over winter EN 5 5 Possible malfunctions EN 5 6 Disposal of the product EN 5 Biolan accessories EN 6 About the guarantee EN 6 BIOLAN GREYWATER FILTE...

Page 4: ...pcs 571513 PP 10 Latch 571507 RST 11 Counter piece 571508 RST In addition to the components illustrated in the component drawing the Greywater Filter 125 also includes Disk valve body 573308 PP Attac...

Page 5: ...125 shall be installed above the ground Place the filter in a location where water will not gather even when there is flooding The filter can be installed out of doors without a cover The unit is the...

Page 6: ...nlet sewer must be insu lated Whether also the outlet sewer needs to be insulated shall be considered case by case 3 2 Putting the filter material in place The filter material is packed in plastic bag...

Page 7: ...e door etc In the lowermost box water flows towards the rear wall from where it falls along the shaped bottom into the discharge sewer 7 Make sure that the unit is on a level both lengthwise and later...

Page 8: ...e and cov ers possible defects in material and workmanship The guarantee does not cover any indirect damage 2 Biolan Oy retains the right to decide about repairing or re placing damaged parts at its d...

Reviews: