![BINMASTER DPM-100 Instruction Manual Download Page 13](http://html1.mh-extra.com/html/binmaster/dpm-100/dpm-100_instruction-manual_2752914013.webp)
DPM-100 Digital Panel Meter Modbus
®
Display
Instruction Manual
13
Panel Mounting Instructions
•
Prepare a standard 1/8 DIN panel cutout -
3.622" x 1.772" (92 mm x 45 mm). Refer to
Figure 1. 1/8 DIN Panel Cutout Dimensions
below for more details.
•
Clearance: allow at least 6.0" (152 mm) behind
the panel for wiring.
•
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to
maintain Type 4X rating: 0.06" (1.5 mm) steel
panel, 0.16" (4.1 mm) plastic panel.
•
Remove the two mounting brackets provided with
the scanner (back-off the two screws so that there
is ¼" (6.4 mm) or less through the bracket. Slide
the bracket toward the front of the case and
remove).
•
Insert scanner into the panel cutout.
•
Install mounting brackets and tighten the screws
against the panel. To achieve a proper seal,
tighten the mounting bracket screws evenly until
scanner is snug to the panel along its short side.
DO NOT OVER TIGHTEN, as the rear of the
panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions
DO NOT
apply AC or DC power to the scanner when using the
Micro USB connection.
Figure 2. Panel Mounting Details
Mounting Dimensions
Figure 3. Scanner Dimensions - Side View
Figure 4. Scanner Dimensions - Top View
Installation Overview
We recommend the following sequence for getting the
scanner into service:
1.
DO NOT
apply AC or DC power to the scanner.
2. Connect the scanner to the PC with the USB
cable provided.
DO NOT
use a different USB
cable.
3. If ScanView (SV) is already installed in your
computer, then the program will launch
automatically in most systems. If the program
does not start automatically, double-click on the
SV icon.
4. If SV is not installed, follow the instructions
provided below.
5. Use SV to configure the scanner for your
application.
6. Disconnect the USB cable from the scanner.
7. Apply power and signal and check operation of
the scanner.
8. Install the scanner and put into service.
9. Make any programming adjustments using the
front panel buttons.
NO
NC
NC
C
NO
C
NO
NC
NC
C
NO
C
+
-
R
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)