CNCR-210/220 • Two-wire 4-20
14
Menu item
Selection
Default settings
Measurement loop name Alphanumeric characters
Sensor
Medium
Liquid
Bulk solid
Liquid
Application liquid
Storage tank, agitator tank, dosing tank, pumping station/
pump shaft, rain overflow basin, tank/ collection basin,
plastic tank (measurement through tank top), mobile
plastic tank (IBC), level measurement in waters, flow
measurement flume/over- flow, demonstration
Storage tank
Application bulk solid
Silo (slim and high), bunker (large
volume), stockpile (point measurement/
profile detection), crusher, demonstration
Silo
(slender and high)
Units
Distance unit of the device
Temperature unit of the instrument
Distance in ft.
Temperature in °F
Adjustment CNCR-210
Max. adjustment (distance A) - 20mA (100%)
Min. adjustment (distance B) - 4mA (0%)
Distance from sensor
Max. adjustment 0.0 m
Min. adjustment 8.0 m
Adjustment CNCR-220
Max. adjustment (distance A) - 20mA (100%)
Min. adjustment (distance B) - 4mA (0%)
Distance from sensor
Max. adjustment 0.0 m
Min. adjustment 15.0 m
Menu item
Selection
Default settings
Damping
Integration time
0 s
Current output
Output characteristics
4 to 20 mA = 0% to 100%
Current range
Min. current 4 mA and
max. current 20.5 mA
Reaction when malfunctions occur
Failure mode < 3.6 mA
Linearization
Linearization type
Linear
Scaling
Scaling size
Scaling unit
Scaling format
0% correspond to 0 l
100% correspond
to 100 l
Display
Menu language
Displayed value
Backlight
English
Distance
On
Access protection
Bluetooth access code
-
Parameter Protection
Deactivated
False signal suppression False signal suppression
0 m
Sounded distance to the material
0 m
Reset
Delivery status, basic settings
-
Menu item
Selection
Default settings
Status
Sensor status
Measured value status
Status output
Status additional measured values
-
Echo curve
Indication of echo curve
-
7 Menu overview