h. Remote Speed Control
28
33 SDV 31
www.binder-es.com
The function of Remote Speed Control allows the operator to control the Output Voltage by an external
potentiometer or a control signal ranging from 1V to 5V. Thus, external remote speed control can be easily
achieved by a PLC, a DCS or some other means.
Remote Speed Control function becomes effective to the controller when the controlling signal exceeds
0.5V. Meanwhile, Remote Speed Control indicator on the panel lights up and the
Vol+
and
Vol-
buttons lose
effectiveness. The LED displayer shows current Output Voltage if the controller is running in the Output
Voltage Adjusting status.
Connection method of the external potentiometer
5. Sensor and Signal Control