Service Manual
MDE 252 Rev. 1
December 2021
Troubleshooting
15
Section 2: Troubleshooting
2.2.12
Alarm on Local Display: Lost Phase
LOST PHASE
1.
The alarm may appear only with 3-phase main power supply.
2.
Generally, it is generated in case of fault or lack of one of the 3 phases that supply the actuator.
3.
Any electrical command is cleared.
Check main voltage supply and frequency on terminals L1, L2 and L3.
The failure is not in the actuator.
Verify failure causes external to Biffi actuator
and possibly in the plant conditions.
Check in sequence:
1.
Verify the actuator electric
parameters on the nameplate or in
the technical data and check that
the external wires sections to the
actuator terminals are correct.
2.
Verify internal wiring between
terminal board (internal screws
terminals) and power supply board
(connector M2).
3.
Verify intern al wiring between
power board (connector CN24) and
logic board (connector CN11).
4.
Replace the power supply board.
5.
Replace the logic board.
Is power supply ok?
NO
YES