4
Design and Function
The DCI-100 Cable identifier is used to identify isolated, de-energized URD
cables. The unit features a transmitter with 2 alligator clips and is powered by 2
Milwaukee, 18V, rechargeable batteries. The unit has 5 LEDs for power, low
battery, pulse operation, short/ open continuity. An optional CT input can be
used when there is excessive neutral current on the cable being tested. The unit
outputs a short duration current pulse that can be detected using one of the
receivers. The receivers available are the STRCV, the AVR receiver, and the
ACDM.
DCI100 TRANSMITTER SET-UP AND TEST
1.
Make sure the unit is off.
2.
Press the button on the front of the 18V Milwaukee Batteries. if there is
less than 2 lights, recharge the battery before operation
3.
Install the batteries by sliding the batteries into the battery holders.
4.
Make sure the alligator clips are not touching and turn the unit on.
5.
The power, and open continuity light should be illuminated and the
pulse light should blink on and off approximately once per second.
6.
Turn the unit off.
7.
Connect the two alligator clamps together.
8.
Turn the unit on.
9.
The power and short continuity lights should be illuminated and the
pulse light should be blinking.
10.
Turn off the unit.
DCI100 TRANSMITTER INSTALLATION
1.
Isolate section of cable to be tested at near end and ground on far end.
2.
Verify voltage is not present on cable being tested using an OSHA
approved test device such as a Bierer voltage detector.
3.
. Install DCI100 as shown in Diagram 1, #1.
4.
Turn unit on.