UPSI-1208DPx
Revision 1-5
25
CONNECTOR
PART NO.
COUNTERPART NO.
V
IN
/V
OUT
Würth Elektronik 691325310004 Würth Elektronik 691364300004
RL
Würth Elektronik 691305140002 Würth Elektronik 691304130002
USB
Würth Elektronik 61400416121
USB type B connector
RS232
D-Sub9 Female
D-Sub 9 Male
F7 Overview connector / counterpart with description / Scope of delivery
SCOPE OF DELIVERY
QUANTITY
DESCRIPTION
1x device
UPSI-1208DP2 or UPSI-1208DP3 - DC UPS
1x
V
IN
/ V
OUT
connector counterpart
1x
Relay connector counterpart
F8 Charging time
Charging times depend on energy storage, input voltage and the load current.
F9 Reverse polarity / Overload / Short circuit
Reverse polarity:
The device has active reverse polarity protection at the input if the input terminal is connected with reverse
polarity while the device is still switched off (e.g. during commissioning). If the device operates in battery mode
and the input terminals are connected with reverse polarity, no reverse polarity protection is given.
Overload:
If the load current at the output is too high, the device switches it off. For maximally allowed current values
and peak current values refer to chapter D „Technical Data”. The status LED indicates the error status by means
of a very rapid flashing sequence. A restart attempt occurs every 10 seconds in normal mode. During battery
mode there is no restart attempt.
Short circuit:
In the event of a short-circuit at the output of the UPS, the output is immediately disconnected (<5 ms). The
status LED indicates the error status by means of a very rapid flashing sequence. A restart attempt occurs every
second in normal mode (non-latch). During battery mode there is no restart attempt. The impact of a short-
circuit to the device depends on length and diameter (impedance) of the output wiring. In case of a short-circuit
directly at the plugs a damage of the device can occur.