Biasi B40/10 Manual And Installation Instructions Download Page 7

PAGE 7 

BIASI B/40 

 

 

 
Locate the boiler to provide sufficient clearance for inspection, servicing and maintenance. 

Minimum clearance to construction or combustible materials shouldn't be less than six (6) inches from 
the top, sides and rear of unit, and eighteen (18) inches from the flue pipe in any direction. Front 
clearance should be at least twenty four (24) inches.   When choosing a location for the boiler, take 
into consideration the 12” supply manifold on the back of the boiler.  Adequate space must be given to 
pipe the manifold in and for the smoke pipe to clear the manifold.  Greater distances for ease of access 
should supersede fire protection clearances. The boiler must be located on a non-combustible floor. A 
smooth, level concrete floor is recommended.  Locate the boiler as close as possible to the chimney.  If 
boiler is  installed on combustible flooring, consult local authorities for proper method of covering 
floor.  The boiler must not be installed on carpeting.  

 
 

Caution: Do not store or use flammable materials, chemicals or flammable liquids, 

especially gasoline, in the vicinity of this heating appliance.

 

 
The boiler location must provide air for proper combustion and ventilation of the surrounding 

area. To burn efficiently, oil requires 30 CFM/GAL.  In general, boiler rooms should incorporate two 
(2) permanent air supply openings, one commencing within 12 inches of the ceiling, and one 
commencing within 12 inches of the floor. These openings

 

should freely communicate with the 

outdoors.  

OUTSIDE AIR: When combustion air is supplied directly through an outside door or wall, 

each opening shall have a free area of one square inch per 4,000 BTUH input for the total input of all 
the appliances in the enclosure. 

INSIDE AIR: When combustion air is supplied from inside the building, each opening shall 

have a free area of one square inch per 1,000 BTUH input for the total of all appliances in the 
enclosure. In no case shall the openings be less than 105 square inches each. 

In both cases, check manufacturers ratings for louver net free area, and correct for screen 

resistance to net free area. 

If the boiler is to be installed where the operation of exhaust fans, attic fans, kitchen 

ventilation systems, clothes dryers or fireplaces may create severe negative vent pressures causing 
unsatisfactory combustion and venting, special provisions should be made for additional make-up air 
to supply the other air requirements.  If building is of tight construction, combustion air requirements 
may not be met and combustion air ducts from outside may be necessary.  Please refer to NFPA No. 
31. 
 

 

Do not install the boiler until the proper combustion air has been arranged

 

4.  Combustion Air Supply:

 

5.  Boiler Location:

 

All manuals and user guides at all-guides.com

Summary of Contents for B40/10

Page 1: ...SMOUTH NH 0380 PORTSMOUTH NH 03801 1 1 1 PHONE 603 PHONE 603 PHONE 603 PHONE 603 334 334 334 334 6400 6400 6400 6400 FAX 603 FAX 603 FAX 603 FAX 603 334 334 334 334 6401 6401 6401 6401 Boiler Manual A...

Page 2: ...fic recommendations We realize that other makes and models of such devices are available and can be used as successfully as those we specify The installing contractor is the best judge of a system s s...

Page 3: ...Block Assembly 6 8 Boiler Trim Kit Installation 7 8 Boiler Tapping Diagram 9 Burner Set up 8 10 Gas Piping 9 12 Breeching and Chimney 10 14 Piping 11 15 Boiler Jacket Assembly 12 17 Boiler Jacket Expl...

Page 4: ...n the installation is completed Do not burn volatile garbage gasoline naphtha or other flammable liquids other than No 2 fuel oil All flammable liquids especially gasoline chemicals rags paper wood sc...

Page 5: ...ay not experience any symptoms only one symptom or a few symptoms Suspect the presence of carbon monoxide if symptoms tend to disappear when you leave your home The following signs may indicate the pr...

Page 6: ...LBS B40 6 6 265 2 20 308 230 86 0 17 34 8 902 B40 7 7 352 2 90 406 305 86 7 20 39 5 1023 B40 8 8 437 3 60 504 380 86 8 23 44 4 1144 B40 9 9 524 4 30 602 456 87 0 26 49 2 1265 B40 10 10 610 5 00 700 53...

Page 7: ...oms should incorporate two 2 permanent air supply openings one commencing within 12 inches of the ceiling and one commencing within 12 inches of the floor These openings should freely communicate with...

Page 8: ...alled on the bottom of the boiler The bottom draw rods should not extend past the front section Draw the sections together until sections make iron to iron contact at a point around the top and bottom...

Page 9: ...on of the front and rear boiler tappings Boiler Model Length L B 40 6 34 8 B 40 7 39 5 B 40 8 44 5 B 40 9 49 2 B 4 10 53 9 B 4 11 58 8 B 4 12 63 9 2 5 MPT Return 2 5 MPT Supply 8 Breech Control Panel...

Page 10: ...2 25 X 60 2 75 X 60 3 25 X 60 3 75 X 60 4 5 X 45 5 50 X 45 Spray Pattern solid solid solid solid solid solid solid Pump Pressure 140 psi 170 psi 175 psi 175 psi 175 psi 160 psi 140 psi Head Position...

Page 11: ...rod settings against manufacturer s specs to insure proper operation 2 Installing properly sized gas piping according to BTU input required and length of gas line run 3 Making sure there is proper man...

Page 12: ...gas piping for various lengths and diameters Locate a drop pipe adjacent to but not in front of the boiler Locate a tee in the drop pipe at the same elevation as the gas inlet connection to the boiler...

Page 13: ...ution The gas valve should not be subjected to more than PSIG Therefore the burner should be isolated during high pressure gas leak tests The appliance and its individual shut off valve must be discon...

Page 14: ...emp so caution should be used when connecting to an outside built chimney Should you have concern that the flue gases could condense then you should consider using a listed power venting unit If power...

Page 15: ...uitable hangars and floor stands not by the boiler It is recommended that the make up water line have a backflow preventer and a pressure reducing valve to reduce line pressure to 10 to 15 psi install...

Page 16: ...BIASI B 40 PAGE 16 All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 17: ...d hex spacers 87 onto the studs Attach the lower mounting bracket 83 to the boiler by using two bolts 89 and screw ing them into the threaded hex spacers Then using sheet metal screws attach the lower...

Page 18: ...dicated breaker in the electric service box A service switch should be mounted on the side of the boiler so the burner man can service the burner and controls The electrical wiring should be routed so...

Page 19: ...Circulator Switch Supplies power to boiler circulator or relay panel It is not suggested to use this switch and it is not utilized in any of the suggested wiring diagrams in this manual 6 Boiler On O...

Page 20: ...BIASI B 40 PAGE 20 B 40 Control Panel Wiring Diagram for Beckett Heat Wise Oil Burner 24V CIRCULATOR RELAY BURNER CONTROL All manuals and user guides at all guides com...

Page 21: ...PAGE 21 BIASI B 40 B 40 Control Panel Wiring Diagram for Beckett Heat Wise Oil Burner Line Voltage CIRCULATOR RELAY BURNER CONTROL All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 22: ...BIASI B 40 PAGE 22 B 40 Control Panel Wiring Diagram for Riello Oil Burner All manuals and user guides at all guides com...

Page 23: ...PAGE 23 BIASI B 40 B 40 Control Panel Wiring Diagram for Heat Wise Gas Burners CIRCULATOR RELAY Burner Primary Control All manuals and user guides at all guides com...

Page 24: ...ush and vacuum combustion chamber and flue passages until all deposits are removed Reassemble components in reverse order making sure any damaged gaskets are repaired or replaced Other maintenance req...

Page 25: ...________________ _________________________ ______________________ Burner Manufacturer Type of Oil Burner Burner Model No Burner Serial No Nozzle Manufacturer Nozzle Spray Angle G P H Type Burner Perfo...

Page 26: ...BIASI B 40 PAGE 26 All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 27: ...PAGE 27 BIASI B 40 All manuals and user guides at all guides com...

Page 28: ...er and that installation conforms to all codes and ordinances 4 This warranty does not apply to boilers which are subject to misuse abuse neglect alteration accident excessive temperature excessive pr...

Reviews: