- 71 -
MAINTENANCE
GAS CONVERSION
8
GAS CONVERSION
8.1 Warnings
The commissioning of this boiler and sys-
tem must only be undertaken by a Gas
Safety Registered Engineer, qualifi ed to
work on Liquefi ed Petroleum Gas (LPG) in
accordance with the requirements of the
Gas Safe Installation and Use Regulations.
Components used to adapt it to the type of
gas available must be genuine parts only.
Factory setting = Natural gas.
8.2
Operations and gas setting
Check that the gas cock mount-
ed on the gas piping to the boiler
is closed and that the appliance
is not powered.
• Remove the body's front panel and turn
the control panel as shown in
section
"MAINTENANCE" to page 73 .
• Unscrew the connector A and
B and re-
move the pipe C ( Fig. 8.1 ).
Fig. 8.1
A
B
C
• Carry out gas conversion by correctly re-
placing the gas restrictor ( Fig. 8.2 ), referring
to the section "Technical data Activ A 12OV"
to page 24
,
section "Technical data Activ
A 15OV" to page 26
,
section "Technical
data Activ A 20OV" to page 28 and section
"Technical data Activ A 25OV" to page 30 .
Fig. 8.2
Gas restrictor
Attention, to reassemble repeat
the operations carried out in re-
verse order. Be careful not to dam-
age the OR gasket of the gas pipe
when inserting the pipe in the air
box (air/gas mixer). After any serv-
ice operation on the components
of the gas circuit check all the
connections for gas tightness.
The factory boiler is set for functioning
with Natural gas (G20).
To set the functioning of the boiler with
LPG
(G31)
gas, carry out the following settings:
• Enter in "programming mode" by pressing
keys 9 - 10 - 11 ( Fig. 8.3 ) for 10 seconds at
the same time until the letters
Pr
that al-
ternate with code
01
are displayed on the
LCD display, indicating that "parameter
01"( Fig. 8.4 ) has been activated.