Biamp Vocia VI-8 Operation Manual Download Page 5

 

 

VI-8 Rear 

Power 

The VI-8 requires an external single 24V DC power source to operate, but is capable of accepting dual 
24V DC inputs for redundancy. Both power sources may be connected concurrently, however each must 
be capable of supporting the full 30 watt load of the unit (inputs are not intended to load-share). Loss or 
return of either power source will not result in an interruption to normal operation as long as one of these 
power sources remains functional. Monitoring of power sources is selectable via the Vocia Software. 

The power connector is a four-way 5.08mm standard header with mating pluggable screw terminal block 
with cable restraint. When power is present at either or both 24V power inputs the corresponding front 
panel green power LED will illuminate. 

CAUTION 

Due to potential energy hazard, connections to the Auxiliary Power DC inputs must be made by a qualified electrician or other 

qualified person as required to conform with all local codes. 

Pin 

Function 

1  DC Power 1 24V(+) 
2  DC Power 1 24V(-) 
3  DC Power 2 24V(+) 
4  DC Power 2 24V(-) 

Device ID 

The rotary ID switches give the unit a unique Device ID. The switches are in hexadecimal format. All units 
of the same device type must have a unique Device ID to function properly within a Vocia Paging World. 
The Factory Default Device ID is 01. A Device ID of 00 is invalid and cannot be used. 

To assign a Device ID of hex 07, leave the MSB switch on 0 and turn the LSB switch to 7. Device ID 
switches should be set using a 0.1 inch (2.5mm) to 0.12 inch (3.0mm) flat blade screwdriver.  

 

NOTE 

Changes made to the Device ID while connected to the network require a power cycle of the device in order to take effect. 

Network Connections 

All CobraNet routing and bundle assignments are processed by the Vocia devices locally. Vocia makes 
dynamic use of available bundles in CobraNet. A 100Base-T Ethernet switch (not repeater hub) is 
required when networking multiple units. CobraNet utilizes standard CAT5, CAT5e, CAT6, or CAT7 
cabling, which has a specified maximum length of 328 feet (100 meters). Additional Ethernet switches, or 
switches which provide fiber-optic interface, can be used to extend the physical distance between units 
within a network. Please note that CobraNet limits network extensions to seven hops (one-way 
transmissions) within a network. The CobraNet network connection is configured with the primary 
connector on the left and the secondary (redundant) connector on the right. The primary and secondary 
CobraNet ports are provided to facilitate connection redundancy. Each connector provides two LEDs that 
indicate Ethernet link and network activity. 

Left LED 

Right LED 

Description 

None 

None 

No Data Connectivity or CobraNet activity 

None 

Green 

Link established 

Flashing yellow 

Green Link established and CobraNet activity detected; The unit is acting as a CobraNet Performer 

Flashing yellow Flashing green Link established and CobraNet activity detected; The unit is acting as a CobraNet Conductor 
Flashing yellow 

None 

CobraNet fault. Check cabling and configuration for errors 

Summary of Contents for Vocia VI-8

Page 1: ...VI 8 OPERATION MANUAL May 2019 585 0348 90A ...

Page 2: ...ss from eight sources via analog mic line level inputs or CobraNet digital audio connections Nine logic inputs can be assigned to various Vocia control events including paging control A logic output and four relay outputs can be assigned to control events The logic output may be used to report status from one or several daisy chained VI 8s to an external system The logic inputs and output are moni...

Page 3: ...ch 44 45 mm high and 19 inch wide rack space with 10 inch 254 mm depth Mounting the unit using four screws with washers will prevent marring of the front panel PVC or nylon washers are appropriate Install the unit away from heat sources such as vents and radiators and in rooms with adequate ventilation Ensure that air can circulate freely behind beside and above the unit Do not exceed the maximum ...

Page 4: ...e severity of the problem Audio may still be passing but if the condition causing the warning is not corrected a failure may occur Flashing amber A Control Input configured as high range monitored input has a Fault Solid amber A chassis Fault is active on the VI 8 Activity Chassis Indicator The VI 8 has an activity LED that will illuminate to show the configuration status of the unit Off The unit ...

Page 5: ...rn the LSB switch to 7 Device ID switches should be set using a 0 1 inch 2 5mm to 0 12 inch 3 0mm flat blade screwdriver NOTE Changes made to the Device ID while connected to the network require a power cycle of the device in order to take effect Network Connections All CobraNet routing and bundle assignments are processed by the Vocia devices locally Vocia makes dynamic use of available bundles i...

Page 6: ... 3 3 Relay NO Channel 1 or 3 4 Relay C Channel 2 or 4 5 Relay NC Channel 2 or 4 6 Relay NO Channel 2 or 4 Control Inputs Nine Control Inputs are available and can be assigned to operate a control input event Input nine has the ability to work as a Status In to allow monitoring of multiple VI 8 devices The Status Out connection can then be reported as a summary alarm to external monitoring systems ...

Reviews: