TABLE “A” - PARAMETERS MENU - (
PARA
)
Parameter
min. max. Default Personal
Definition
Description
TCA
0
180
10
Automatic closing time [s]
Waiting time before automatic closing.
TRF.LGHT.CLR.T
1
180
40
Time-to-clear traffic light
zone [s]
Time-to-clear for the zone run through by traffic controlled by the traffic
light.
alar ti e
10
240
30
Alarm time
[s]
If an obstacle is sensed or the photocells are engaged for longer than the set
time, contact 26-27 closes. The contact is then opened by the Stop command
or by the closing limit switch. Active only by setting the AUX3=5 logic.
o p e n . c a l i b .
(Special par. 1)*
0
100
82
Opening value calibration
Opening value calibration [%]
Set the reference value from 0,0 to 100,0 for the required opening position
(see Paragraph Limit Switch Setting).
c l o s . c a l i b .
(Special par. 2)*
0
100
21
Closing value calibration
Closing value calibration [%]
Set the reference value from 0,0 to 100,0 for the required closing position
(see Paragraph Limit Switch Setting).
accel.
(Special par. 6)*
1
99
75
Acceleration
Acceleration [%]
Set the acceleration to be applied at the beginning of each movement.
OP.FORCE
1
99
85
Leaf force during opening
[%]
Force exerted by the barrier while opening.
WARNING: It affects impact force directly: make sure that
current safety requirements are met with the set value (*).
Install anti-crush safety devices where necessary (**).
CLS.FORCE
1
99
85
Leaf force during closing
[%]
Force exerted by the barrier while closing.
WARNING: It affects impact force directly: make sure that
current safety requirements are met with the set value (*).
Install anti-crush safety devices where necessary (**).
BRAKE
0
85
50
Braking [%]
Opening speed/Closing [%]
Set the numerical value of the speed: 1% corresponds to the slow-down
speed, 99% to the maximum speed.
e er.bra e
75
99
75
Emergency braking
Emergency braking [%]
Set a value from 75% to 99% for the braking intensity in case of reversing
movement or emergency braking: any values lower than those set in the
“braking” parameter will be ignored.
Op. speed
15
50
50
Speed during opening
Running speed during opening [%]
Sets the running speed that the barrier must reach during opening, as a
percentage of the maximum speed the actuator can reach.
cl speed
15
50
50
Speed during closing
Running speed during closing [%]
Sets the running speed that the barrier must reach during closing, as a
percentage of the maximum speed the actuator can reach.
Maintenance
0
250
0
Programming number of
operations for maintenance
threshold
[in hundreds]
Allows you to set a number of operations after which the need for main-
tenance will be reported on the AUX output configured as Maintenance
or Flashing Light and Maintenance .
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
(**) Impact forces can be reduced by using deformable edges.
(
***)=Reference for universal handheld programmer.
TABLE “B” - LOGIC - (
LOGIC
)
Logic
Definition
Default
Cross out
setting
used
Optional extras
TCA
Automatic Closing
Time
1
0
Logic not enabled
1
Switches automatic closing on
FAST CLS.
Fast closing
0
0
Logic not enabled
1
Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse.
15.8) PASSWORD MENU (
PASSWORD
)
Used to set a password for the board’s wireless programming via the U-link
network.
With “PROTECTION LEVEL” logic set to 1,2,3,4, the password is required to
access the programming menus. After 10 consecutive failed attempts to log
in, you will need to wait 3 minutes before trying again. During this time,
whenever an attempt is made to log in, the display will read “BLOC”. The
default password is 1234.
16) CONNECTION WITH EXPANSION BOARDS AND UNIVERSAL HANDHELD
PROGRAMMER VERSION> V1.40 (Fig. M) Refer to specific manual.
WARNING! Incorrect settings can result in damage to property and injury to people
and animals.
17) U-LINK OPTIONAL MODULES
Refer to the U-link instructions for the modules.
17.1) Opposite Barriers
(Fig. N)
Refer to the U-link instructions for the modules.
NOTE: On the board set as the Slave, the Safety Edge input (Safety Edge/ Test
Safety Edge/ 8k2 Safety Edge) should only be set to SAFE2.
18) RESTORING FACTORY SETTINGS (Fig.
O
)
WARNING:
this operation will restore the control unit’s factory settings and all
transmitters stored in its memory will be deleted.
WARNING! Incorrect settings can result in damage to property and injury to
people and animals.
- Cut off power to the board (Fig.
O ref.1)
- Open the Stop input and press the - and OK keys together (Fig.
O ref.2)
- Switch on the board’s power (Fig.
O ref.3)
- The display will read RST; confirm within 3 sec. by pressing the OK key (Fig.
O ref.4)
- Wait for the procedure to finish (Fig.
O ref.5)
- Procedure finished (Fig.
O ref.6)
19)
PARKING MANAGEMENT SYSTEM CONNECTION
The board has an output for the control of the barrier status configured this
way (Fig. I4).
The logic must be set to
AUX3/AUX0=12.
closed
contact between terminals
26-27
with the barrier
lowered
open
contact between terminals
26-27
with the barrier
not lowered.
MICHELANGELO BT A-
47
D812218 00100_05