VALUE
FUNCTION
0
START EXTERNAL
–
●
●
●
1
START INTERNAL
–
●
●
●
2
OPEN
●
●
●
3
CLOSE
●
●
●
4
●
●
●
5
TIMER (HOLD OPEN)
●
●
●
6
●
●
●
7
●
●
8
●
●
9
●
●
10
SAFETY EDGE (bar)
●
●
11
OBSTRUCTION, SUPERVISED
●
12
OPENING OBSTRUCTION, SUPERVISED
●
13
CLOSING OBSTRUCTION, SUPERVISED
●
14
SAFETY EDGE, SUPERVISED
●
IC & EXPI LOGICS
IC 1 & 2 EXPI 1 EXPI 2
PED (PARTIAL OPEN)
TIMER PED (HOLD PARTIAL OPEN)
OBSTRUCTION (phot)
OPENING OBSTRUCTION (phop)
CLOSING OBSTRUCTION (phcl)
error
description
error
description
er20
motor 2 improper encoder movement detected
er35
motor 1 obstacle detection during opening
er22
motor 2 opposite movement
er36
motor 1 obstacle detection during closing
er25
motor 1 improper encoder movement detected
er37
motor 1 obstacle detection during opening slowdown
er27
motor 1 opposite movement
er38
motor 1 obstacle detection during closing slowdown
er30
motor 2 obstacle detection during opening
er40
thermal overload
er31
motor 2 obstacle detection during closing
er61
operating on battery power
er32
motor 2 obstacle detection during opening slowdown
error setting limits
er33
motor 2 obstacle detection during closing slowdown
erf9
lock output overload
ersw
V A L U E
0
1
2
L O G I C
4-STEP
3-STEP
2-STEP
O PEN I N G
STOPS + TCA STOPS + TCA REVERSES
C L O S I N G
STOPS
REVERSES
REVERSES
STEP-BY-STEP LOGICS
VALUE
FUNCTION
0
2ND CHANNEL RECEIVER OUTPUT
1
GATE OPEN LIGHT. output active WHEN GATE IS NOT CLOSED. FLASHES WHILE CLOSING
2
COURTESY LIGHT. output active DURING AND FOR 90 SECONDS AFTER OPERATION.
3
GATE NOT CLOSED. output active UNTIL CLOSE LIMIT IS REACHED
4
START OF CYCLE. output active FOR 1 SECOND AT THE BEGINNING OF EACH CYCLE
5
GATE OPEN ALARM. output active IF GATE IS HELD OPEN FOR MORE THAN DOUBLE THE TIMER TO CLOSE TIME
6
GATE RUNNING. output active WHILE MOTORS ARE POWERED
7
SOLENOID LOCK. output active FOR 2 SECOND AT THE BEGINNING OF OPEN CYCLE
8
MAGNETIC LOCK. output active WHEN GATE IS CLOSED
9
AUX & expo LOGICS
TRAFFIC LIGHT CONTROL (EXPANSION BOARD OUTPUT WITH TLB BOARD ONLY)
*note - when the expansion board
input 1 (expi 1) is set to values 11 ~ 14,
the expansion board input 2 (expi 2)
automatically becomes the
supervision circuit (fault).
advanced programming of inputs and outputs
DOWN
ENTER
UP
escape
navigating the programming menu
button
navigation
value edit
[+]
scrolls up
increase value
[-]
scrolls down
decrease value
enter
enter value
[+] & [-]
escape
escape
[ok]
press the [ok] button rapidly twice to enter programming
VALUE
FUNCTION
DESCRIPTION
0
OBSTRUCTION SENSOR INPUT, NON-CONTACT
1
OBSTRUCTION SENSOR INPUT, NON-CONTACT, supervised (fault active)
2
OPENING OBSTRUCTION SENSOR INPUT, NON-CONTACT
3
OPENING OBSTRUCTION SENSOR INPUT, NON-CONTACT, supervised (fault active)
4
CLOSING OBSTRUCTION SENSOR INPUT, NON-CONTACT
5
CLOSING OBSTRUCTION SENSOR INPUT, NON-CONTACT, supervised (fault active)
6
BAR
SAFETY EDGE (CONTACT OBSTRUCTION) INPUT
7
BAR TEST
SAFETY EDGE (CONTACT OBSTRUCTION) INPUT, supervised (fault active)
8
BAR 8K2
SAFE LOGICS
PHOT
PHOT TEST
PHOT OP
PHOT OP TEST
PHOT CL
PHOT CL TEST
SAFETY EDGE (CONTACT OBSTRUCTION) EOL RESISTOR SUPERVISED INPUT
common error codes
MAIN
SELECTION
DESCRIPTION
DEFAULT
RANGE
PARAM >
OPEN DELAY TIME
Motor 2 opening delay in seconds
1
0-10
Motor 1 closing delay in seconds
1
0-10
TCA
Auto-close time adjustment in seconds
10
1-180
Traffic zone clear time adjustment in seconds
40
1-180
Slowdown starting distance from end of open travel expressed in percentage
10
0-50
Slowdown starting distance from end of close travel expressed in percentage
10
0-50
Slowdown starting distance from end of open and close travel expressed in percentage
15
0-50
OP. FORCE
Percentage of opening force exerted over the AUTOSET value before obstruction is sensed
50
1-99
Percentage of closing force exerted over the AUTOSET value before obstruction is sensed
50
1-99
OP SPEED
Motor opening speed expressed in percentage
99
15-99
CL SPEED
Motor closing speed expressed in percentage
99
15-99
SLOW SPEED
Slowdown speed expressed in percentage from maximum speed.
25
15-99
LOGIC >
MOTOR TYPE
1=Eli 250; 2=Phobos BT, 3=Igea BT
0
0-3
TCA
Timer to Close Automatically. 0=OFF / 1=ON
0
0-1
Closes when sensors are cleared. 0=OFF / 1=ON
0
0-1
STEP-BY-STEP MOVEMENT *
Determines how the system reacts when a START command is received during operation
0
0-2
Gate running output (AUX value=6) closes 3 sec. before gate movement. 0=OFF / 1=ON
0
0-1
HOLD-TO-RUN
Requires continuous OPEN or CLOSE command input for gate to operate. 0=OFF / 1=ON
0
0-2
Ignores START input during the opening cycle. 0=OFF / 1=ON
0
0-1
Ignores the START input while counting down for automatic closing. 0=OFF / 1=ON
0
0-1
Ignores the START input during the closing cycle. 0=OFF / 1=ON
0
0-1
RAM BLOW C. OP
Pushes gate against physical stop before opening
0
0-1
RAM BLOW C. CL
Pushes gate against physical stop before closing
0
0-1
BLOC PERSIST
Hourly push against physical stop
0
0-1
Pushes gate against physical stop for .5 seconds after close limit has been reached.
0
0-1
ICE
Continuous force learning on every operation.
0
0-1
1 MOT. ON
Single Motor operation. 0= (2)motors; 1=(1)motor.
0
0-1
OPEN IN OTHER DIRECT.
0 = Pull to open; 1 = Push to open
0
0-1
SAFE 1 *
0
0-8
SAFE 2 *
Configuration of safety input terminal 74. Defaulted as Bar (Safety Edge)
6
0-8
Configuration of command input terminal 61. Defaulted as Start E
0
0-6
4
0-6
AUX 3 *
0
0-8
FIXED CODE
Rolling code defeat. 0 = rolling code; 1 = fixed code
0
0-1
Quick remote programming. 0 = disabled; 1 = enabled
1
0-1
SERIAL MODE
0 = Slave unit; 1 = Master unit
0
0-1
ADDRESS
Unit's network identification number.
0
0-127
Configuration of Expansion board input 1. Defaulted as Start command.
1
0-14
Configuration of Expansion board input 2. Defaulted as Start command.
0
0-10
EXPO 1 *
Configuration of Expansion board output 1. Defaulted as Traffic light control..
9
0-9
EXPO 2 *
Configuration of Expansion board output 2. Defaulted as Traffic light control..
9
0-9
Red light flashes for 3 sec. at every start. 0 = Off; 1 = On
0
0-1
TRAFFIC LIGHT RED LAMP ALWAYS ON
Red light remains on when gate is closed. 0 = Off; 1 = On
0
0-1
RADIO >
ADD START
Learns transmitter button as START command
ADD 2CH
ERASE 64
Erase complete memory
COD RX
Show receiver ID Code
WK
W LINK.
DEFAULT
Restores board to factory settings. No effect on RADIO
LANGUAGE >
Italian
French
German
ENG
English
ESP
Spanish
AUTOSET
Operates motor(s) several times and automatically adjust its FORCE settings
L. SW ADJ
Limit of travel adjustment. Only available with type 4 and 5 motors
STAT >
Displays board firmware version.
N. CYCLES
Displays number of hundreds of cycles (001=100; 010=1000; 100=10,000)
N. REMOTES
Displays the number of remotes in memory.
ERR
Displays the last 30 board errors in descending order.
PASSWORD
Password setting for wireless programmer
CLS DELAY TIME
TRF. LGHT.CLR. T
OP. DIST. SLOWD
CL. DIST. SLOWD
DIST. DECEL
CLS. FORCE
FAST CLS.
PRE-ALARM
IBL OPEN
IBL TCA
IBL CLOSE
PRESS SWC
Configuration of safety input terminal 72. Defaulted as Phot (Obstruction)
IC 1 *
IC 2 *
Configuration of command input terminal 62. Defaulted as Ped (Partial open)
Configuration of auxiliary output terminals 26 & 27. Defaulted as 2
nd
channel contacts.
RADIO PROG
EXPI 1 *
EXPI 2 *
TRAFFIC LIGHT PREFLASHING
Learns transmitter button as 2
nd
channel
ITA
FRA
DEU
VERS