
SECTION 4
MAINTENANCE
Servicing Notes
Servicing should be carried out annually by a competent person such as a GAS
SAFE registered engineer.
This is a condition of the guarantee schemes.
The service should include visually checking the chimney and fire opening for
accumulations of debris and a smoke test to check for a positive up-draught in the
chimney. The oxypilot on the burner unit must also be changed as a condition of
the guarantee. The condition of the fuel-bed should be checked and
if necessary
the whole item should be replaced with a genuine replacement item.
The
burner assembly is designed to be removed as a complete unit for ease of access.
After any servicing work a gas tightness check must always be carried out.
For Diagrams refer to Section 2
4.1
Removing the burner assembly from the fire.
4.1.1
Prepare work area (lay down dust sheets etc.)
4.1.2
Remove the glass panel
4.1.3
Isolate the gas supply and remove the supply pipe from the appliance
inlet elbow. Unscrew and remove the four off screws which retain the
ceramic support plate to the base, then lift clear. Remove the two off
screws which hold the burner in position & then slide burner unit
forwards to remove from side support channels.
4.1.4
To refit the burner assembly, locate the burner unit and refit the two off
screws. Refit the ceramic support plate and four off screws. Refit the
gas supply pipe and carry out a gas tightness test. Re-fit the glass
panel.
4.2
Removing the Gas Control Valve - RC / EFC models
4.2.1
Remove the burner assembly as detailed in section 4.1
4.2.2
Remove the thermocouple wires from the valve, remove the
main pipe, inlet pipe, pilot pipe from the valve. Take note of position of
coloured terminals on thermocouple wires as valve will not function
correctly if these are replaced the opposite way round.
4.2.3
Unclip the valve from its mounting bracket. Re-assemble in reverse
order and carry out a gas tightness test.
37