EI90

Fire damper BSKC9

1.   Make a hole for size in question (d + 5mm).

2.   Apply fire sealant on the wall, 20 mm around the 

 periphery of the hole.

3.   Secure the damper flat and tight with the installation kit 

placed in the groove as shown in the photo. Make sure 
that the shape of the damper is not impacted when 
mounting.

4.   Seal joints between the installation kit and damper 

casing with fire sealant.

5.   When installing without a duct connection, the  damper 

should be fitted with an incombustible grille. The 
 minimum distance between the open damper blade 
and grille should be 50 mm.

Installation in wall, fire resistance class EI90

Damper’s fire resistance class: EI90 (ve ho i <–> o) S.

EG-certificate 0402-CPR-SC0051-19

6.  The duct system is fitted in accordance with current    

requirements. Ensure that suspension and duct 
 systems do not affect the movement of the damper 
blade.

•  Damper for installation in walls and floors with fire re-

sistance class EI90. 

•  The shortest distance between dampers must be  

200 mm.

•  The minimum distance to the connecting structure 

should be 75 mm.

•  Free position on damper spindle.

 

 

d+5

Installation kit*

Screw 5x65 mm

Seal acc. to section 2 and 4.

Duct

Duct

Min. thickness 95 mm

Installation instructions

* Installation kit (sleeve rings)

* Installation kit (sleeve rings)
  Ø100-315 = 3 parts with 3 screws in each
  Ø400-630 = 4 parts with 4 screws in each

Summary of Contents for BSKC9

Page 1: ...18 01 2022 www bevent rasch com BSKC9 Circular fire damper FIRE SAFETY...

Page 2: ...ts from the smoke detector This must be fitted in the ventilation duct near the damper or in another suitable location Smoke detectors are monitored by means of Bevent Rasch s monitoring sys tem or th...

Page 3: ...8 dampers RCKD RD Smoke detectors RCTU RCTC MRB3 system max 236 dampers FENIX2 max 2 dampers FENIX4 FENIX max 16 dampers Specification Installation options for BSKC9 Size Fire class Wall of drywall E...

Page 4: ...ings Union piece Illustrated in de energised state Wiring diagram Tf1 Tf2 BAT72 Actuator S N L1 M 1 2 1 2 3 4 5 6 5 80 Thermal sensor Acuator Actuator type BFL BFN Sizing max 4 VA 6 VA Running time mo...

Page 5: ...0 1000 100 45 50 55 60 Air flow l s Total pressure drop Pa Sound power level LW dB 1 10 100 200 10 1000 100 45 50 55 60 65 Air flow l s Total pressure drop Pa Sound power level LW dB 1 10 100 200 10 1...

Page 6: ...wer level LW dB 1 10 100 200 100 1000 3000 50 55 60 65 Air flow l s Total pressure drop Pa Sound power level LW dB Correction of sound power level LWok in octave band Lwok Lw Kok Sound data Correction...

Page 7: ...ade and grille should be 50 mm Installation in wall fire resistance class EI90 Damper s fire resistance class EI90 ve ho i o S EG certificate 0402 CPR SC0051 19 6 The duct system is fitted in accordan...

Page 8: ...installing without a duct connection the damper should be fitted with an incombustible grille The minimum distance between the open damper blade and grille should be 50 mm 6 The duct system is fitted...

Page 9: ...late the duct from the hole in the wall to the actuator of the damper Insulate the duct system EI90 according to the supplier s instructions 8 The duct system is fitted in accordance with current requ...

Reviews: