![BETTENERGY ELESHELL-10.2K User Manual Download Page 28](http://html.mh-extra.com/html/bettenergy/eleshell-10-2k/eleshell-10-2k_user-manual_2743147028.webp)
ELESHELL
28
LDHEB-6100 is greater than 80A, the battery protection device will open. Solution: if
the working current is too large, please change the setting on the power side.
4
)
High voltage: if the battery voltage is higher than 57.6v or above, the battery
charging protection will be turned on. Solution: if the battery is fully charged, please
discharge it for a period of time. If the charging voltage is too high, please change the
setting on the power side.
5
)
Low voltage: when the battery is discharged to 49v or lower, the battery
discharge protection will be turned on. Solution: charge the battery until the red light
goes out. In addition to the above five points, if you still can't find the fault, please
turn off the battery and contact us.
3.
In multiple battery parallel systems, the SOC LED are different.
1
)
When the first installation, please charge in full first to balance the capacity gap;
2
)
If the minimum SOC LED indicator is less than 1 of the maximum SOCLED
indicator, in operation and the SOC LED indicator is restored within 1 0 minutes,
normal operation;
3
)
Before expanding the battery capacity, charge the online battery to 45%-50%SOC;
Summary of Contents for ELESHELL-10.2K
Page 1: ...ELESHELL 1 User Manual Model ELESHELL 6 1 10 2 14 3K ...
Page 5: ...ELESHELL 5 ...
Page 19: ...ELESHELL 19 6 4 Installation Instructions 6 4 1 Overall Dimensions ...
Page 20: ...ELESHELL 20 Minimum Installation distance between the battery pack and equipment ...
Page 21: ...ELESHELL 21 6 5 Connection of all wires Step 1 fix the battery ...
Page 22: ...ELESHELL 22 Step 2 connect the power cord S ...
Page 23: ...ELESHELL 23 Tep 3 connect the internal communication line ...
Page 31: ...ELESHELL 31 ...