33
1100 Installation Planning
The information in this section will help you prepare the location of the Axxium Pro system. Section 1303
describes the various configurations for input and output power connections.
1101 Dimensions
The table below contains overall cabinet dimensions and
empty cabinet weights.
Table 8. UPS Dimensions
* Add the following weights for isolation transformers:
3-slot cabinet:
65 lb (30 kg)
6-slot cabinet:
140 lb (64 kg)
12-slot cabinet:
275 lb (125 kg)
Optional floor anchor kit weighs 9 lb (4 kg)
Each battery module weighs 30 lb (13.6 kg)
Each power module weighs 17 lb (7.7 kg).
1102 Equipment Clearances
All cabinet sizes require the following clearances to allow for servicing and adequate ventilation.
Sides (from side panels): 6 in. (152 mm)
Top and back: 12 in. (305 mm)
Front: 36 in. (915 mm)
If flexible conduit connects the UPS to the service and load distribution panels, you may be able to gain access
for servicing by moving the UPS. If this is the case, you must still leave 12 in. (305 mm) clearance at the back
and 6 in. (152 mm) at the sides of the UPS for ventilation. Do not block the ventilation holes on each side and
the back of the unit.
External battery cabinets may be installed with bases tight against the UPS cabinet base and against each other.
A
B
C
115
(52)
25.5
(650)
17.0
(430)
33.25
(845)
6-slot (with
caster cart)
196
(89)
28.5
(725)
24.0
(610)
60.75
(1545)
12-slot
78
(35)
25.5
(650)
158
(72)
28.5
(725)
24.0
(610)
47.0
(1195)
9-slot
17.0
(430)
103
(47)
25.5
(650)
17.0
(430)
31.5
(800)
6-slot
19.5
(495)
66
(30)
25.5
(650)
17.0
(430)
17.75
(450)
3-slot
3-slot (with
caster cart)
Weight*
lb (kg)
Depth (C)
in. (mm)
Width (B)
in. (mm)
Height (A)
in. (mm)
Cabinet
Size
Figure 9. UPS Dimensions