If there is more than one point that have ground fault, you are suggested to find out the point of fault that
has strongest signal and step by step to all the other faults.
Fig 2.7
2.8 Location for Other Ways of Fault
2.8.1 Wire Mix-connection
Location of mix-connection fault is same like that of ground fault location. The difference is that signal
generator injects the current signal in the two lines that are mix-connected (see Fig 2.8.1 for wiring
instruction). Then trace the current signal with the signal receiver in the same rules like ground fault
location as explained before.
If both of the two lines are accidentally grounded, they are mix-connected through the earth. Then
please check the ground fault of each line as DC ground fault location described previously.