DKAC-I / MBAC-I
- Climate gateway
Programming manual
v1.0
www.besknx.com
18
Cyclic: It sends a bit telegram ‘1’ to the bus each time the limit value is exceeded cyclically.
Name
Period of time
Values
Communication object / Constant value
Description It is the count time of the timer. It can be configured as a constant value or a value received through the
bus with one of the following communication object formats:
1 byte (dpt 5.010): Value from 0 to 255 (x 100 ms)
2 bytes (7.004): Value from 0 to 6553500 ms
2 bytes float (9.010): Value from 0 to 670760 s
Name
Duty
Values
1 byte (dpt 5.010), 2 bytes (7.004) or 2 bytes float (9.010)
Description Only visible if timer type PWM is selected. It is the time that the output signal is at high level (“1”) within
the period of time. Its value can be received through the bus with one of the following communication
object formats:
1 byte (dpt 5.010): Value from 0 to 255 (x 100 ms)
2 bytes (7.004): Value from 0 to 6553500 ms
2 bytes float (9.010): Value from 0 to 670760 s
Ouput 1
0
Enable 1
0
Period T
0
Value
Time
T