Bernini Be242 AMF ATS Installation Manual Download Page 20

Be242     Be242RB                OEM's Manual    V3.X.XX -   

January  -  2021           page 20 

 

20 

 

 

 
 
Follow the instructions: 

 

A) -

 Remove the battery power supply; disconnect all connectors, disconnect the Mains/Generator plugs. 

B) -

 Push and hold the [ACK-F10] pushbutton, apply the Vdc power supply; all LEDs and Display turn on. 

C) -

 Release the button when you have verified all indicators; the LEDs will turn off and the message [- - - -] will 

be displayed.  
 

NOTE - At this stage of the TEST, if the display indicates one of the codes contained in Table13.1 or 13.2, 

the Be242 is damaged and should be returned to Bernini Design. 

 

To exit the Troubleshooting, remove the Vdc supply at anytime 

 
 
 
 
 
 

 

13.1 Testing the Pushbuttons 

 

A) -

 Push the pushbuttons on the front panel one by one. The display will show a message according to Table 

13.1. As soon as you release all buttons, the message [- - - -] will be displayed. 
 
 

 
Table 13.1: Pushbuttons true table 
 

Pushbutton 

Display  

Code

 

Pushbutton

 

Display 

Code

 

[START-F1]

 

[ F1 ]

 

[OFF-F7 ]

 

[ F7 ]

 

[STOP-F2]

 

[ F2 ]

 

[AUTO↓]

 

[auto]

 

[ I-F3 ]

 

[ F3 ]

 

[TEST↑]

 

[tESt]

 

[ O-F4 ]

 

[ F4 ]

 

[←F8]

 

[ F8 ]

 

[ I-F5 ]

 

[ F5 ]

 

[F9→]

 

[ F9 ]

 

[ MAN-F6 ]

 

[ F6 ]

 

[ACK-F10]

 

[ F10]

 

 
 

 

13.2 Testing the Inputs 

 

Push and hold the [ACK-F10] button until the message [-in-] appears. Connect, one by one, inputs #9 to #14 to 
the battery minus. For each input, a code will be displayed according to Table 13.2. If more than one input is 
connected together (or some of them in short circuit), the display indicates the messages in sequence.  

 

Table 13.2 

Terminal number 

(function) 

Display  

Code

 

 

Terminal number 

(function)

 

Display 

Code

 

#14  (Input 4) 

 

[ inP 4]

 

#9 (Low fuel)

 

[ FUEL]

 

#10  (Input 3) 

 

[ inP 3]

 

#12 (Temperature)

 

[ tEMP]

 

#13  (Input 2) 

 

[ inP 2]

 

#11 (Oil pressure)

 

[ oiL]

 

 

[

 

#JH1-JH4 (Emergency)

 

[ EMEr]

 

 
 
 
 

Summary of Contents for Be242 AMF ATS

Page 1: ...o extra charge The buyer shall provide sufficient information on any alleged defects in the product so as to enable BD to determine their cause and existence If the Be242 is not defective or the produ...

Page 2: ...LEDs 5 0 2 21 2 3 Lamp Test 5 1 Lo U Under Voltage 7 02A P 09 Lock Remote Lock E03 4 10 Low Battery voltage 4 10 Er 13 Log Events 4 30 Mains Failure 7 01A P 01 Mains Restore 7 01B P 02 Maintenance tim...

Page 3: ...lt settings page 10 6 30 Reading the parameters page 10 6 40 Activating the password page 11 6 50 Changing the password page 11 6 60 Removing the password page 11 7 0 Programmable Param tre page 11 Ta...

Page 4: ...of the software example 1 0 01 and the detected kind of battery 12V or 24V Should the battery supply to be lower than 7 5V the BE242 will trigger the ER 13 alarm code the software will not run The mo...

Page 5: ...ned off and a dot on the display will blink slowly Push one of the pushbuttons on the front panel to activate the display 2 2 MANUAL mode Note default programming for emergency input is normally close...

Page 6: ...ts the green indicator V blinks slowly see table 7 01 7 02 2 4 TEST mode Push the TEST pushbutton until the green LED illuminates The Be242 starts the engine and transfers the load to the Generator if...

Page 7: ...age of the Mains 60 V up to 998 V If the Mains is simulated the display will show the message n on nXXX V R S XXX V S T _XXX L R T F8 or F9 U on ACK F10 Generator Frequency 20Hz up to 70Hz GXXX Hz F8...

Page 8: ...ameter P 34 section 7 table 7 04 InP 3 Input 3 Shutdown Warning see 7 07 Er 08 Emergency Shutdown see parameter P 35 section 7 table 7 04 InP 4 Input 4 Shutdown Warning see 7 07 Er 09 Emergency Shutdo...

Page 9: ...ed 6 10 Enter the Programming Mode 1 Provide a voltage from a battery supply of over 11 5 V Push the OFF F7 pushbutton to enter the OFF mode the LEDs and display turn OFF the dot on the right side of...

Page 10: ...nter the OFF mode without saving the parameters You can select a mode of operation as indicated in section 2 0 6 20 Re programming Default settings The parameters of the Be242 are programmed in factor...

Page 11: ...F9 pushbuttons simultaneously until the SAVE message appears approximately 5 seconds the Be242 saves the password and remains in PROGRAM mode To exit push the OFF pushbutton 6 60 Removing the passwor...

Page 12: ...de Description Default Min Max Options P 3 Contactors changeover This timing introduces a delay between the switching of the contactors 2 0 1secs 15 0secs P 4 Under voltage limit If the Phase to Phase...

Page 13: ...own without a cooling down time Mode3 The Be242 provides a warning if the parameters rise above the setting for the specified timing The setting is allowed in step of 5 Amps by using the pushbutton on...

Page 14: ...Engine Cooling time 15 0 59 mins P 25 Stop Solenoid timing Energized to stop 15 1 sec 59 mins P 26 Alternator Crank termination Push F1 8 0 3 0 V 30 0 V oFF Belt break setting Push F2 8 0 3 0 V 30 0 V...

Page 15: ...oFF disabled Parameter Code Description Default Min Max Options P 40 EJP time 5 1 sec 99 mins P 41 Periodic Test interval see 16 10 oFF 2 hours 9999 h oFF P 42 Periodic Test duration see 16 10 5 1 mi...

Page 16: ...ooling and Stop 17 Horn silence 4 Bypass Cooling and Stop 18 Display Right Pushbutton 5 Warning only 19 Display Left Pushbutton 6 Bypass and Warning 20 Overload Input Warning 7 Remote Manual Mode 21 O...

Page 17: ...tatus 14 NOT USED 46 Pre glow MODE 1 2 3 4 15 Low Battery Voltage Warning 47 NOT USED 16 High Battery Voltage Warning 48 RENT 48h 17 Low Fuel Shutdown switch 49 RENT 0h Expired 18 NOT USED 50 Engine R...

Page 18: ...tes all alarms Section 9 0 Hour Meter To clear or pre load the counter use the following instructions 1 Enter the programming mode as indicated in sections 6 10 6 20 2 Select the parameter P 51 by mea...

Page 19: ...otection This is accomplished by programming a voltage setting in the P 26 sub menu To test the efficiency of this protection disconnect terminal D from the charger alternator and connect to ground th...

Page 20: ...nt panel one by one The display will show a message according to Table 13 1 As soon as you release all buttons the message will be displayed Table 13 1 Pushbuttons true table Pushbutton Display Code P...

Page 21: ...ement Precision Vdc 1 Dimensions 224X105 X 68 mm Cut out round 56mm min Be242RB Dim 195X126 X 70 mm Rail mount Operating Temperature range 30 deg C up to 70 deg C Humidity Range 5 up to 95 non condens...

Page 22: ...mmend that you program the P 31 to 15 number of attempts in order to provide proper time for AUTOSTART to start the engine 16 30 Single Phase operation Program the parameter P 8 with the option 3 as i...

Page 23: ...o the AC1 rating of the contactors and according to the size of cables and terminal blocks In case of short circuit when the automatic protections fail you can trust to an additional external overcurr...

Page 24: ...Be242 Be242RB OEM s Manual V3 X XX January 2021 page 24 24...

Page 25: ...18 Current Trasf 2 22 L1 Generator 3 Start Solenoid 11 Low Oil Pressure 19 Current Trasf 3 24 L1 Generator 4 Stop Solenoid 12 High Temperature 20 Common CTs 24 KG Output 5 Output 2 13 Input 2 JC SUB...

Reviews: