-4-
ELECTRIC HEATER DATA* Add total motor amp draw from Table #2 to circuit #1 for unit total amp draw
MODEL
KW
208V 1Ø
240V 1Ø
208V 3Ø Amp Draw
240V 3Ø
Amp Draw
460V 3Ø**
Amp Draw
600V 3Ø**
Amp Draw
Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1
Circuit 2 Circuit 3
Circuit 1 Circuit 2
Circuit 1
Circuit 1
AHC10-1036
9.5
45.7
-
39.6
-
26.4
-
-
22.9
-
11.4
9.5
AHC10-1042
9.5
45.7
-
39.6
-
26.4
-
-
22.9
-
11.4
9.5
AHC10-1048
9.5
45.7
-
39.6
-
26.4
-
-
22.9
-
11.4
9.5
AHC10-2048
12.5
20.0
40.1
17.4
34.7
34.7
-
-
30.1
-
15.0
12.6
AHC10-2060
16.0
-
-
-
-
44.4
-
-
38.5
-
19.2
16.1
AHC10-2072
19.0
-
-
-
-
26.4
26.4
-
22.9
22.9
22.9
19.1
AHC10-2084
19.0
-
-
-
-
26.4
26.4
-
22.9
22.9
22.9
19.1
AHC10-2096
19.0
-
-
-
-
26.4
26.4
-
22.9
22.9
22.9
19.1
AHC10-3096
25.0
-
-
-
-
34.7
34.7
-
30.1
30.1
30.1
25.1
AHC10-3108
28.5
-
-
-
-
26.4
26.4
26.4
22.9
45.7
34.3
28.6
AHC10-3120
28.5
-
-
-
-
26.4
26.4
26.4
22.9
45.7
34.3
28.6
*Optional kW available. Check wiring diagram supplied with unit for kW and AMP draw if not listed above.
** Separate 120V, 208V or 240V single phase circuit required to operate motors.
Table 3
V. TOP MOUNTING -
INDOOR INSTALLATION
(CEILING SUSPENSION)
For top mounting suspension rods, four (4) factory installed
5
/
16”
threaded inserts are located on the top of the unit.
See Figure 6.
1. Install the ARCHITECTURAL HIGH PERFORMANCE 10
Air curtain so that nothing interferes with the curtain of air
when it is deflected 20° to either side. If the air stream strikes
any obstruction, i.e. the top edge of the doorway, a structural
beam, a door opening device, etc., its efficiency will be greatly
reduced.
See Figure 2.
2. Follow instructions 2 and 3 under INDOOR INSTALLATION:
WALL MOUNTING (on page 1) checking to assure the minimum
clearances are met.
3. Attach
5
/
16”
threaded rods, or other suitable hardware to the
top mounted threaded inserts.
VI. ELECTRICAL CONNECTIONS
All electrical wiring and connections
MUST
be performed by
qualified personnel in accordance with the latest edition of the
National Electrical Code ANSI/NFPA No. 70 or, in Canada, the
Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local
codes and regulations.
MAKE SURE THE CORRECT VOLTAGE AS
MARKED ON THE UNIT IS USED.
The ARCHITECTURAL HIGH PERFORMANCE 10 Air curtain is
internally wired to the junction box(es) on top of the of the unit.
1. Run the proper size cable from the source to the junction box
and connect the leads.
2. Wiring diagrams are located inside the junction box. For amp
rating,
See Tables 2 or 3
and the name plate on the unit.
VII. ELECTRICALLY HEATED MODELS
The heater circuit may be controlled by a remote thermostat, a
built-in thermostat or a manual on/off heater switch located on
the discharge side of the unit.
See Figure 7.
1. If a thermostat is used, connect the proper leads located in
the junction box to the leads of the thermostat. (See wiring
diagram located in the junction box)
2. If a manual heat on/off switch is used, factory wiring is supplied
from the heating coil to the unit mounted heat on/off switch.
Overheat protection is provided by thermal cutouts built
into the heater coil assembly. (See the wiring diagram
located in the junction box.)
Figure 6
5/16" Recessed Insert
Side View
Suspension Rods