216
Standards and certifications • Requirements for immunity to disturbances (immunity)
Automation PC 820 User's Manual V 1.20
4.8 Damped vibration
DC power inputs
-
20 interruptions for 10 ms < UN -
15%, criteria A
Test carried out according to
EN 61000-4-12
Limits according to
EN 61131-2
Power I/O, L to L
±
1 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Power I/O, L to PE
±
2.5 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Table 152: Test requirements - Damped vibration
Test carried out according to
EN 61000-4-11
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Table 151: Test requirements - Voltage dips, fluctuations, and short-term interruptions (cont.)