INTELLIBUS 

 

Number  : NR 1157 

 

Revision : B 

 

Page 1/19 

 

INSTRUCTIONS FOR START-UP 

 

 

 

 
 
 
 
 

Instructions for start-up 

 

INTELLIBUS FF 

 

FOUNDATION FIELDBUS FOR  

( 2801) 

 
 
 
 
 
 
 
 

 

 

Summary of Contents for INTELLIBUS FF

Page 1: ...INTELLIBUS Number NR 1157 Revision B Page 1 19 INSTRUCTIONS FOR START UP Instructions for start up INTELLIBUS FF FOUNDATION FIELDBUS FOR INTELLI Intelli 2801...

Page 2: ...supply 6 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 6 4 1 Foundation Fieldbus communication 6 4 1 1 Link Active Scheduler 6 4 1 2 Function Block 7 4 1 3 Transducer Block 7 4 1 4 Device description 7 4...

Page 3: ...ieldbus interface described in this document has been specially designed for the Bernard actuators with INTELLI control Control box with inside Foundation Fieldbus interface could be supplied to conne...

Page 4: ...ieldbus module INTELLIBUS FF located in the actuator is plugged on to the main Intelli board and no access is needed Connection box INTELLI board Button for local control Display INTELLIBUS board FPX...

Page 5: ...hielding End of line termination A termination has to be installed at each end of line This termination is not built in the actuator 3 4 Set up The INTELLIBUS module is selected in the menu Use the lo...

Page 6: ...e The right position is then updated through the fieldbus communication 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 4 1 Foundation Fieldbus communication 4 1 1 Link Active Scheduler The INTELLIBUS FF in...

Page 7: ...g torque position curve see 5 4 1 4 Device description To achieve interoperability Device Description DD technology is used The DD is like a driver for a printer L Bernard supply the Device Descriptio...

Page 8: ...tance x current Total fieldbus length 1 to 7 is less than 1900m Spurs length 3 6 is less than 120m The last actuator has a supply voltage of 24V 1 2 4 5 7 22V 9V that is enough to work 4 2 3 Terminato...

Page 9: ...ree technologies is to keep the communication speed unaffected and therefore to get a very short response time L Bernard can supply weatherproof or explosion proof repeaters 5 CONTROLS AND INDICATIONS...

Page 10: ...e open and close commands have to be maintained If this command is set to 1 a short duration open close command pulse is sufficient to drive the valve to the open or closed position In this case the s...

Page 11: ...rational The test consists to operate the actuator on a partial stroke and return The start position and the stroke can be configured An alarm is emitted if the stroke is not performed in a predetermi...

Page 12: ...1 0 No command 1 Auxiliary command 2 Bit 2 0 No command 1 Close command Bit 3 0 No command 1 Open command Bit 4 0 Relay 1 contact open 1 Relay 1 contact closed Bit 5 0 Relay 2 contact open 1 Relay 2...

Page 13: ...allowed from Local controls SELECTOR TO OFF no command allowed in local or from Fieldbus Indications are always available SELECTOR TO LOCAL No command allowed from Fieldbus Indications are always ava...

Page 14: ...ked motor open Bit 6 0 No locked motor close alarm 1 Locked motor close Bit 7 0 No overtravel alarm 1 Overtravel alarm TORQUE LIMITER ACTION OPEN CLOSE torque limiter action in opening closing directi...

Page 15: ...n 5 is active ESD input by default The connection depends of actuator type Refer to the actuator wiring diagram ACTUATOR RUNNING the actuator is operated in opening or closing direction STOP MID TRAVE...

Page 16: ...orque 3 open and close on torque 1 read only 7 Stroke unit 1 number of turns 2 degrees 3 mm 1 read only 8 Set up for auxiliary command 1 Bit state for active command see 4 1 0 not used 1 local 0 remot...

Page 17: ...nds 2 read write 19 Operating time without timer in seconds 2 read write 20 no local stop in remote mode 0 local stop possible 1 no local stop 1 read write 21 Fail safe position in case of loss of com...

Page 18: ...t 1 read only 43 locked motor close 0 no fault 1 fault 1 read only 44 torque sensor 0 no fault 1 fault 1 read only 44 position sensor 0 no fault 1 fault 1 read only 46 Closing direction of rotation di...

Page 19: ...t into fieldbus devices as needed to achieve the desired device functionality For example a simple temperature transmitter may contain an AI function block The control valve actuator might contain a P...