4. Installation 

4.1 

Before the valve is installed, flush the pipeline to remove any dirt, scale, debris, etc. Not flushing the line might 
result in the valve being inoperable. 

4.2 

In cases where the valve is used for individual pump pressure-relief, locate the relief valve between the pump 
and the pump discharge check valve. It shall be attached in a way that it can be readily removed for repairs 
without disturbing the piping.  

4.3 

Allow enough room around the valve assembly for any adjustments and future maintenance/disassembly work. 

4.4 

Install the valve in the pipeline with the valve flow arrow on the body casting in the proper direction.  Use the 
lifting eye provided on the main valve cover for lifting and lowering the valve.  

4.5 

For best performance, install the valve horizontally with the cover up. However, other positions are acceptable. 
Ensure that the valve is positioned so that the actuator can be easily removed for future maintenance. 

4.6 

After installation, carefully inspect/correct any damaged accessories, piping, tubing, or fittings. Ensure that there 
are no leaks. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 730-UF

Page 1: ...change without notice BERMAD shall not be liable for any errors contained herein All Rights Reserved Copyright by BERMAD Control Valves IOM Model FP 730 UF Sizes 2 12 PI7PE09 730 UF Bermad Pressure Re...

Page 2: ...pump service The double chambered actuator design enables quick and smooth valve action According to the inlet pressure the pilot valve regulates the main valve throttling This valve requires only ex...

Page 3: ...ischarge check valve It shall be attached in a way that it can be readily removed for repairs without disturbing the piping 4 3 Allow enough room around the valve assembly for any adjustments and futu...

Page 4: ...contained in this document is subject to change without notice BERMAD shall not be liable for any errors contained herein All Rights Reserved Copyright by BERMAD Control Valves IOM Model FP 730 UF Siz...

Page 5: ...actory pre set adjusted pressure 5 4 Slowly allow system flow so that system pressure falls below the relief valve adjusted pressure The relief valve should slowly shut to drip tight Readjusting Tools...

Page 6: ...ned in accordance with the Maintenance Instructions of the plant this Maintenance Manual as well as the Standard for the Inspection Testing and Maintenance of Water Based Fire Protection Systems NFPA...

Page 7: ...dle valve 21 not properly adjusted Factory set at or 1 open Adjust Valve fails to regulate Air trapped in main valve cover Loosen cover tube fitting at the highest point allow the air to escape and re...

Reviews: