IOM
Model: FP
-
730
-
UF
Sizes: 2"-
12
"
PI7PE09-730-UF
4. Installation
4.1
Before the valve is installed, flush the pipeline to remove any dirt, scale, debris, etc. Not flushing the line might
result in the valve being inoperable.
4.2
In cases where the valve is used for individual pump pressure-relief, locate the relief valve between the pump
and the pump discharge check valve. It shall be attached in a way that it can be readily removed for repairs
without disturbing the piping.
4.3
Allow enough room around the valve assembly for any adjustments and future maintenance/disassembly work.
4.4
Install the valve in the pipeline with the valve flow arrow on the body casting in the proper direction. Use the
lifting eye provided on the main valve cover for lifting and lowering the valve.
4.5
For best performance, install the valve horizontally with the cover up. However, other positions are acceptable.
Ensure that the valve is positioned so that the actuator can be easily removed for future maintenance.
4.6
After installation, carefully inspect/correct any damaged accessories, piping, tubing, or fittings. Ensure that there
are no leaks.