IOM

Model: FP 400E-5D

 

Sizes:  2"-12"

PI4PE09-400E-5D 

Hydraulically Controlled, On-Off Deluge Valve 

1.

Safety 

First

BERMAD believes that the safety of personnel working with and around our equipment is the most important 
consideration. Please read all safety information below and from any other relevant source before attempting to 
perform any maintenance function. 
Comply with all approved and established precautions for working with your type of equipment and/or 
environment. 
Authorized personnel should perform all maintenance tasks. 
Prior to performing a procedure, read it through to the end and understand it. If anything is not clear, ask the 
appropriate authority. 
When performing a procedure, follow the steps in succession without omission” 

2.

Description

BERMAD Hydraulically Controlled Deluge valve with 5D trim is actuated by an HRV - Hydraulic Relay Valve 
(26B), which permits local release of top chamber pressure (instead of the usual remote top chamber release by 
the hydraulic release system), in order to ensure quick opening even when the release device is distant. 
The Deluge Valve requires a wet pilot line system including hydraulic releases.  
The HRV (26B) is normally held closed by pressure maintained in the hydraulic release system. 
The 5D trim may also use a Normally Closed hydraulic release system with thermostatic releases and/or fixed 
temperature releases to release water pressure directly from the Deluge Valve top chamber. 

In fire conditions, operation of a releasing device on the hydraulic release system causes pressure in the release 
system piping to drop, causing the HRV to open, releasing to the atmosphere trapped water pressure from the 
top chamber and opening the Deluge Valve, allowing water to enter the system piping.  
The releasing device in the Normally Closed hydraulic release system holds the pressure in the top chamber of 
the Deluge Valve. The opening of the device in a fire condition releases trapped water pressure from the top 
chamber, opening the Deluge Valve allowing water to enter the piping system. Water will flow from any open 
sprinklers and/or spray nozzles on the system. 
Deluge systems are commonly used where, when the system operates, it is desirable to simultaneously spray 
water from all open sprinklers and/or nozzles on the system. 

3.

  Australian Standard SSL

BERMAD  400E-5D  Deluge  Valve  is 

Australian  Standard  SSL

  when  installed  with  specific  components  & 

accessories.

4.

Installation

Subject to all other instructions, drawings and technical specifications which describe the Bermad Deluge Valve, 
install in their proper positions the components comprising the Deluge Trim Package, according to the drawing 
relevant to the specific valve, hereby enclosed. 
Install also the additional accessories, which appear in the drawing and which must be installed as shown in the 
drawing, although they are not packed together with the Bermad Deluge Valve itself. 
Any deviation in trim size or arrangement may adversely affect the proper operation of the Deluge Valve. 
Refer also to NFPA 13 or the applicable installation standards, codes and authorities having jurisdiction. 

Summary of Contents for 400E-5D

Page 1: ...hout notice BERMAD shall not be liable for any errors contained herein All Rights Reserved Copyright by BERMAD Control Valves IOM Model FP 400E 5D Sizes 2 12 PI4PE09 400E 5D Bermad Hydraulically Controlled On Off Deluge Valve Model 400E 5D INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD ...

Page 2: ...and or fixed temperature releases to release water pressure directly from the Deluge Valve top chamber In fire conditions operation of a releasing device on the hydraulic release system causes pressure in the release system piping to drop causing the HRV to open releasing to the atmosphere trapped water pressure from the top chamber and opening the Deluge Valve allowing water to enter the system p...

Page 3: ...del FP 400E 5D Sizes 2 12 PI4PE09 400E 5D 4 1 The Deluge Valve and trim must be installed only in areas where they will not be subjected to freezing temperatures Note Pilot height value should not exceed that appearing on Table 1 Maximum Allowed Elevation Above Valve 4 2 All the hydraulic release system devices such as Thermostatic releases and or fixed temperature releases must be compatible for ...

Page 4: ...contained in this document is subject to change without notice BERMAD shall not be liable for any errors contained herein All Rights Reserved Copyright by BERMAD Control Valves IOM Model FP 400E 5D Sizes 2 12 PI4PE09 400E 5D Figure 1 Installation Drawing ...

Page 5: ...e hydraulic release system to the HRV 26B and to the top chamber of the Deluge Valve 7 4 When the pressure gauge on the top chamber indicates full service line pressure and is no longer rising the release system is reset 7 5 Check the entire release system for leaks 7 6 Open the system control valve slowly No water should flow into system 7 7 Depress the Drip Check 19B and drain any water from the...

Page 6: ...g against the valve seat 9 sealing it drip tight and keeping the system piping dry The HRV is held closed by the pressure in the wet pilot line Under FIRE or TEST conditions a pilot line hydraulic pressure drop opens the HRV causing water to exit through the Accelerator faster than it can be supplied Pressure is then released from the main valve s control chamber through the opened HRV or the Manu...

Page 7: ...mplete Weekly and Monthly inspections 16 2 Place the system out of service See instructions above 16 3 Trip the release line system clean all strainers 4A 4B and priming line restriction 2 16 4 The interior of the Deluge Valve should be inspected and cleaned 16 5 The interior of the HRV including its Diaphragm and Seal should be inspected and cleaned 16 6 Place the system back in service See instr...

Page 8: ...estriction 2 B Leaking release system C Leaking Release System D Damaged deluge valve seat HRV out of order 17 4 Deluge Valve Will Not Reset Check for any of the following possible causes A An open main control valve B System not properly drained C Closed priming line valve 18B D Damaged Deluge Valve seat or seal E Foreign object lodged between seal disc and valve seat F HRV 26B not properly seale...