picture 3: Adjuster for run-on time of output HLK
(1) Flush-mounted insert
(10) Adjuster for run-on time of output
HLK
o
Turn adjuster (10) to the desired time.
6 Appendix
6.1 Technical data
Rated voltage
AC 230 V ~
Mains frequency
50 / 60 Hz
Ambient temperature
+5 ... +35 °C
Circuit breaker
max. 10 A
Contact type
µ contact
Switching current at 25 °C, Kanal 1
Ohmic
10 A
Switch-on current max. 4 s at 10% switch-on
time
15 A
Minimum switching current AC
100 mA
Connected load at 25 °C, Kanal 1
Incandescent lamps
1000 W
HV halogen lamps
1000 W
Inductive transformers
750 VA
Tronic transformers
750 W
Fluorescent lamps, uncompensated
500 VA
Electronic ballast
Type-dependent
Connection, Kanal 1
Single stranded
max. 4 mm²
finely stranded without conductor sleeve
max. 4 mm²
finely stranded with conductor sleeve
max. 2.5 mm²
HLK
Follow-up time
approx. 2, 10, 30, 60, 120 min
Switching voltage
AC 230 V ~
Minimum switching voltage
AC 12 V~
Switching current for AC 230 V ~, 25 °C, HLK
Ohmic
6 A
Switch-on current
max. 2.1 A
Minimum switching current AC
100 mA
Connected load for 230 V ~, 25 °C, HLK
Incandescent lamps
800 W
HV halogen lamps
750 W
Seite 5/6
30.07.2010
82541321
97-09545-000
BLC
BLC relay insert HVAC