
OPERATION
Preparing to Start the Pump – Deep Well
Never run pump dry.
Running pump without
water may cause pump to overheat, damaging seal and pos-
sibly causing burns to persons handling pump. Fill pump with
water before starting.
Never run pump against closed discharge.
To do so can boil water inside pump, causing hazardous
pressure in unit, risk of explosion and possibly scalding per-
sons handling pump.
1.
Open the control valve as far as possible (See Figure
13). Then remove the priming plug from the pump and fill
the pump, fill all piping between the pump and the well,
and make sure that all piping in the well is full. If you
have also installed a priming tee in the suction piping,
remove the plug from the tee and fill the suction piping.
2.
Replace all fill plugs and close the control valve com-
pletely (See Figure 14).
3.
Power on! Start the pump and watch the pressure gauge.
The pressure should build rapidly to 50 psi as the pump
primes.
4.
After 2 or 3 minutes, the gauge should show pressure. If
not, stop the pump, remove the fill plugs, reopen the con-
trol valve, and refill the pump and piping. You may have
to repeat this two or three times in order to get all the
trapped air out of the piping. Don’t forget to close the
control valve each time before you start the pump.
5.
When pressure has built up and stabilized at about 50
psi, slowly open the control valve (See Figure 15) and let
the pressure drop until the pressure gauge needle starts
to flutter. When the needle flutters, close the valve just
enough to stop the flutter (See Figure 15). Your pump is
now operating at its most efficient point.
9
Open control
valve as far as
possible and
fill pump and
piping through
priming port
or priming tee.
Figure 13 – Fill Pump
Replace all
fill plugs and
completely
close control
valve .
Figure 14 – Prime Pump
C-Close Control Valve until Pressure
Stabilizes
A-Open Control Valve
B-Watch for Pressure Gauge to Flutter
Figure 15 – Set Control Valve
Max. Load
Branch Fuse
Distance in Feet from Motor to Supply
Model
Volts
Amps
Rating Amps*
0 - 100
101 - 200
201 - 300
301 - 400
401 - 500
3PL
115/230
8.8/4.4
15/15
14/14
12/14
10/14
8/14
8/12
5PL
115/230
12.2/6.1
20/15
12/14
10/14
8/14
6/12
6/12
7PL
115/230
14.8/7.4
20/15
12/14
8/14
6/14
6/12
4/10
10PL
115/230
16.2/8.1
25/15
10/14
8/14
6/14
6/12
4/10
10PLS11C
115/230
14.8/7.4
20/15
12/14
8/14
6/14
6/12
4/10
15PLS11C
115/230
16.2/8.1
25/15
10/14
8/14
6/14
6/12
4/10
WIRING CHART – RECOMMENDED WIRE AND FUSE SIZES
(*) Fusetrons are recommended instead of fuses on all motor circuits.