1.6. Intended use
The device is a component of a modular automation system for industrial control applications in
the medium to high performance range.
The automation system is designed for use in overvoltage category I (IEC 364-4-443) for the con-
trol and regulation of machinery and industrial processes in low-voltage installations in accord-
ance with the following basic conditions.
→
Maximum rated supply voltage of 1,000 V AC (50/60 Hz) or 1,500 V DC
→
For use in an environment with max. category 2 level of pollution (EN 60950)
→
For use in a maximum altitude of 2,000 m a.s.l.
→
For indoor use in areas not exposed to direct UV radiation
→
Max. ambient temperature inside and outside the control cabinet according to the technical specifi-
cations (see “Technical data”).
Correct and safe operation of the automation system requires qualified project planning, proper
transport, storage, installation and use as well as careful maintenance.
The automation system may only be used within the scope of the information and applications
specified in this documentation and associated user handbooks.
The automation system must only be used as follows:
→
As intended
→
In technically perfect condition
→
Without unauthorised modifications
→
By qualified users only
Observe the rules of the employers' liability insurance association, the German Technical
Inspection Association (TÜV), the Association of German Electrical Engineers (VDE) or rele-
vant national regulations.
The device is intended for installation in control cabinets in industrial machines and systems in in-
door areas.
For operation, refer to the applicable ambient conditions
Protect the device from condensation and moisture.
Operation
If the device has been stored or transported in cold weather or under conditions of large
fluctuations in temperature, do not start to operate it until it has acclimatised to room tem-
perature for the place in which it is used.
Wait at least 12 hours after it has reached room temperature before operating the device.