Parameter Configuration and Description
Level 1 – Accesses only basic operator parameters.
Level 2 – Accesses all parameters including those in Level 1.
5.1
Programming
Refer to Figures 4.1 and 5.1. To change the default Data Code in a given parameter:
A. Press the STOP key to stop the inverter if running.
B. Press the PROGram key to enter Level 1 Program mode. To enter Level 2 press and
hold the SHIFT key and then the PROGram key. The PRG indicator will turn on.
C. Press the UP/DOWN arrow keys to access the desired parameter. The parameter
number will be displayed in the upper left corner of the digital display.
D. Press the SHIFT key to allow the Data Code to be changed. PRG will starts to blink.
E. Press the UP/DOWN arrows to select the new Data Code.
F. Press the ENTER key to store the new Data Code. The display shows STOred for one
second.
G. Press the PROGram key to exit the Program mode or the UP/DOWN arrows to select a
new parameter.
5.2
Parameter Descriptions
The following section contains functional descriptions of all parameters. The number in the
“LEVEL” column indicates the programming level in which access to the parameter in ques-
tion is possible. Access to all parameters is possible in level 2 (also to parameter in level
1). A “V” means that this parameter only has a view function, while “P” stands for program-
mable.
This parameter holds the identification code of the Read Only Memory.
This defines the nominal output current of the inverter and serves as the 100% reference
for all current measurements. Continuous drive capacity is 1.1 times 03-IRAT. Your ACP
3000 inverter can provide 110% of this rating continuously without damage or tripping.
Figure 5.1
PARAMETER DESCRIPTION
UNIT LEVEL
02-RVLVL – Software Revision
2V
03-IRAT
– Inverter Rated Current
[A]
2V