Operating Instructions
3-349-868-74
3/8.18
Edited in Germany • Subject to change without notice • PDF version available on the Internet
Electronic
Energy Meters
Efficio Certified
Direct Meter BME
Transformer Meter BME
1
Scope of Delivery
1
Energy meter
2
Operating instructions (German and English)
Operating instructions can be found at
www.berg-energie.de
2
Safety Precautions – Symbols
– Check the specified nominal voltage on the serial
plate before placing the instrument into service.
– Observe maximum pulse output voltage.
– When wiring the instrument, make sure the connec-
tor cables are not damaged, and that they are volt-
age-free.
– If it can be assumed that safe operation is no longer
possible, the instrument must be immediately
removed from service (disconnect input voltage!).
Safe operation can no longer be relied upon if the
instrument demonstrates visible damage.
The device may not be placed back into operation
until troubleshooting and repair have been per-
formed, and calibration and dielectric strength have
been tested and approved at our factory or an autho-
rized service center.
– Voltage conducting parts may be exposed if the
cover is opened.
If balancing, maintenance or repair of a live open
instrument is required, this may only be carried out by
trained personnel who are familiar with the dangers
involved.
– When connecting measuring current, it is important
to provide for low-ohmic contact and to select an
appropriate conductor diameter.
Meanings of Symbols on the Instrument
DE MTP 18 B 004 MI-003
(Direct Meter)
DE MTP 18 B 005 MI-003
(Transformer Meter)
Prototype test certificate
Total insulation,
protection class II device
Warning concerning a point of danger
(attention, observe documentation!)
This device may not be disposed of with the
trash. Further information can be accessed on
the Internet at www.berg-energie.de.
Metrology mark
with indication of year (M18) and register
no. of the notified body for module D,
country-specific calibration validity period
Marking with stamp of the federally approved
test laboratory
(for recalibration only)
Tamper-Proof Sealing – Opening the Meter / Repairs
Tamper-Proof Calibration Sealing
with Manufacturer’s Seal
(at the side)
If the manufacturer’s seal is damaged or removed, all
guarantee claims are rendered null and void.
The meter may only be opened by authorized, trained per-
sonnel in order to ensure flawless operation and to assure
that the guarantee is not rendered null and void.
If it can be ascertained that the meter has been opened
by unauthorized personnel, no guarantee claims can be
honored by the manufacturer with regard to personal
safety, measuring accuracy, compliance with applicable
safety measures or any consequential damages.
Tamper-proof sealing for the terminal cover
may be
attached either to the left or the right of the terminal
cover.
3
Rating Plate Entries
4
Connector Pin Assignments and Wire Gauge
Note:
Observe the wiring diagrams in the top and bot-
tom terminal covers.
Meas. Inputs, Direct Meter (top & bottom terminals)
Meas. Inputs, Transformer Meter (bottom terminals)
Connections (top terminals)
5
Pulse Output
Default setting: active energy
Terminal 23 (S01) import, terminal 25 (S02) export
* Type of energy can also be selected with feature Impuls.
Underlined values are default values.
* Pulse rates are based on secondary side
!
M18
1948
EBY
8
18
Connections
Direct Meter
Transformer Meter
Current input
Solid wire
≤
16 sq. mm
Fine wire
≤
25 mm
2
or
≤
16 mm
2
with wire end ferrule
Tightening torque:
3-4 Nm
Solid wire
≤
4 sq. mm
Tightening torque:
0,5-0,6 Nm
Voltage input
N: solid wire
≤
2.5 sq. mm
Tightening torque:
0,4 Nm
Solid wire
≤
4 sq. mm
Tightening torque:
0,5-0,6 Nm
SØ pulse output
Bus output, tariff input
(power utility pulse)
Solid wire
≤
2.5 sq. mm
Tightening torque:
0,4 Nm
Solid wire
≤
2.5 sq. mm
Tightening torque:
0,4 Nm
TCP/IP
RJ45 (8P8C)
Prototype test certificate
Accuracy class / operating temperature
←
Energy export /
→
energy import
Nominal voltage
Imin - In (Imax.) / nominal frequency
Warning
Protective insulation
Symbol for system type
Year of manufacture
Metrology mark
LED constant
2D code
EBY
8
18
Serial number
Up key
Enter key
Anti-reversing
for
the registers in both
energy directions
Bidirectional meter
L2
L1
L3
Voltage
Voltage
Current
Current
Current
Voltage
Current
Current
Current
N
Voltage
Voltage
Voltage
Current
Current
Current
L3
L2
L1
N
Current
Current
Current
Tariff
Connections
W1:
LON
W2:
M-Bus
W4: TCP/IP
W7:
Modbus RTU
V1 ... 9: SØ pulse output
Tb Tn Ta
TCP/IP
Pulse Rates
programmable V2
Direct Meter
1
…
1000 Imp/kWh
Transformer *
CT, VT progr.
1
...
1000
...
50000Imp/kWh
R
L
+
24
23/25
U
t
Energy type*
Max. 40 V
24 V DC
I = max. 27 mA
U
External Voltage Source
Standard pulse duration: 30 ms + 5%, interpulse period: > 30 ms
V7/V8 pulse duration: 130 ms + 5%, interpulse period: > 130 ms
6
Display and Control Panel
6.1
Test LEDs
The
test LEDs
are located above the control keys. The left-
hand LED indicates energy export, and the right-hand LED
energy import. LED blinking frequency increases along
with measured power. If all currents are smaller than start-
ing current, both LEDs light up continuously.
LED Constant
Direct Meter:
10,000 pls/kWh
Transformer Meter: 100,000 pls/kWh
6.2
Resolution, Main Display (large characters) Energy Import
Intern wird mit erhöhter Auflösung gezählt. Hierdurch kann bei
Mehrtarifnutzung das Gesamtregister in der letzten Stelle
einige Digit über der Summe der Einzelregister liegen.
* An additional place to the right of the decimal point is included
for the calibration display in the case of a main display which
can be calibrated. And thus the leading digit is eliminated in
the case of an 8-place display.
** Due to programmable CT, VT only the secondary display can be
calibrated. Therefore, display overflow is based on the secondary
display. The normal display is shifted one place to the left if neces-
sary.
6.3
Meanings of Symbols at the LCD
u
Main display
, not calibrated
(programmable CT/VT, see section 6.2).
T1 ... T8: active tariff
Display of instantaneous power in 4 quad-
rants: positive or negative active power P,
positive or negative reactive power Q.
Correct connection:
Continuous illumination of the phase symbols
where P
≥
0
Phase failure:
Symbol for affected phase is cleared from the display.
Incorrect phase sequence:
Phase symbols blink in following order: 3 - 2 - 1.
Negative power:
Respective phase symbol blinks.
For bus connection: appears when
the meter transmits a data packet.
Key symbols for parameters configuration
(see next column)
Key Symbols for Parameters Configuration
for Feature Q1 and V2:
Key and 2
nd
key bit blanked
:
Parameter CT, VT and SØ configurable according
to features, disabling with enable key.
Key displayed with one bit:
Parameter CT, VT and SØ disabled,
change after activating the enable key.
6.4
LCD Background Illumination
Background illumination is activated each time a key is
activated. Background illumination goes off after about
2 minutes.
Background illumination colors indicate various display
menus:
– White: query menus
– Red: display of firmware version
– Pink: parameters display and setting menu
– Blinking red: in case of error
6.5
Key Operation
Querying Parameter Values
In addition to the LCD test, the
UP
and
ENTER
keys also
make it possible to query currently set parameter val-
ues, as well as to change parameters for certain fea-
tures after first pressing the
enable key
(located behind
the top cover).
If no keys are pressed for a period of 1 minute, the
meter is returned automatically to its standard display.
Parameters can be changed for the following meters:
Parameters CT and VT for Transformer Meter,
Parameter SØ for Pulse Meter.
Further parameters in accordance with interface descri-
tion.
a) Enabling Parameter Changes
The enable key makes it possible to enable or disable
parameter changes. It’s located underneath the top ter-
minal cover between terminals 21 and 22 and is acti-
vated with a pointed object (e.g. a ballpoint pen).
Pressing the enable key activates the “change parame-
ters” operating mode (key off):
Pressing the enable key again disables the “change
parameters” operating mode (key on):
If no keys are pressed for a period of about 2 minutes,
the “change parameters” operating mode is exited auto-
matically and disabled (key on).
b) Changing Parameter Values
➭
Briefly press the enabling key as described in point
a) above (this activates the “change parameters”
operating mode).
➭
See the operating overview on the back with regard
to changing the parameters.
➭
Press and hold the
ENTER
key until the firmware ver-
sion appears (red background).
➭
Press the
UP
key. The display test appears.
Briefly press and hold the
ENTER
key in order to dis-
play two further test patterns.
➭
Then repeatedly press the
UP
key until the parame-
ter to be changed appears at the display.
➭
Briefly press the
ENTER
key in order to access the
setting menu.
➭
The input cursor blinks at the leftmost entry posi-
tion. Each tine the
ENTER
key is pressed the cursor
is advanced to the next position to the right. The
value of the blinking digit can be increased by
pressing the
UP
key. When the rightmost digit is ac-
knowledged by pressing the
ENTER
key, the se-
lected value is accepted and SAVinG appears
briefly at auxiliary display 2. If no keys are pressed
for a period of about one minute, the setting menu
is exited.
➭
Press and hold the
ENTER
key or wait for one minute
in order to change to the normal display.
➭
Press the enable key once again. This disables the
“change parameters” operating mode.
Disabling takes place automatically after 2 minutes.
Meter
CTxVT
min.
CTxVT
max.
Normal dis-
play
Calibration
display *
Unit
Direct
Meter
—
—
123456,78
23456,789
kWh
Trans
for-
mer
meter
Q1
**
1
4 u12345,67
**
kWh
5
40 u123456,7
**
kWh
41
400
u1234567
**
kWh
401
4000 u12345,67
**
MWh
4001
40000 u123456,7
**
MWh
40001
100000
u1234567
**
MWh
Main display
(active energy* in kWh or MWh)
Auxiliary display 1
(active power*
in kW or MW)
* Transformer meter: CT and VT are taken into account
Auxiliary display 2
(e.g. IN, OUT for import or export)
In case of error: error code alternates with current display
(reactive energy* in kVArh or MVArh)
(reactive energy or power in kVAr(h) or MVAr(h)*)
Power: negative sign for export
Enable Key
→
→
Repair and Replacement Parts Service
Recalibration
Recalibration can be conducted at any time by our fed-
erally approved test laboratory.